![background image](http://html.mh-extra.com/html/ge/gek-106273l/gek-106273l_instruction-manual_134819197.webp)
ANNEX 5 HARMONIC FILTERING
15-2
MIF Digital Feeder Protection
GEK-106273L
15.2
DIGITAL FILTER
The first operation performed by the CPU with the voltage and/or current signal samples is the DFT.
The Discrete Fourier Transformation consists in decomposing a signal into a series of sinusoidal signals with
frequencies that are multiples of the fundamental frequency. If after this operation, we take the fundamental
frequency signal, and we disregard the rest of signals (harmonics), we will get a harmonic filter. This action is
performed by the MIF relay.
The MIF uses a complete cycle recursive DFT, that is, for each sample it calculates the phasor from the
previous sample phasor and the difference between the current sample and the previous cycle sample. This makes
the relay require a complete cycle to obtain the correct measure value.
In the following figure (figure 2), we can see how the measure is established from a signal value that changes
from 0 to 1.
Figure 3 shows the answer from the digital filter with the frequency. The figure shows how all the high level
harmonics are eliminated. This makes the MIF suitable for applications where it is necessary to filter any type of
harmonic, for example, the 2
nd
and 3
rd
, which are the most commonly found in electrical lines.
Figure 2
Figure 3
0
0 , 2
0 , 4
0 , 6
0 , 8
1
1 , 2
2 0
3 0
4 0
5 0
6 0
7 0
8 0
9 0
1 0 0
1 1 0
1 2 0
1 3 0
1 4 0
1 5 0
1 6 0
1 7 0
1 8 0
1 9 0
2 0 0
2 1 0
2 2 0
F r e q u e n c y
5 0 H z
6 0 H z
MEASURE
0
0,2
0,4
0,6
0,8
1
1,2
0
15
30
45
60
75
90
SAMPLES
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...