RELAY COMMISSIONING
9-8
MIF Digital Feeder Protection
GEK-106273L
9.16.6.
ANSI EXTREMELY INVERSE CURVE
•
Set the relay as follows:
51P Settings Group
Curve EXTREMELY
INVERSE
Time Dial
5
•
Apply 0.9 times the pickup current into phase C and the relay should not trip.
•
Apply 1.5 times the pickup current and the relay should trip between 17.19 and 23.58 sec.
•
Apply 5 times the pickup current and the relay should trip between 1.14 and 1.34 sec.