KEYPAD AND DISPLAY
GEK-106273L
MIF Digital Feeder Protection
8-17
The mnemonics in figure 8.10 stand for:
TRIP 50PH
50PH Permission to Trip
Range:
Y/N.
TAP 50PH
50PH Current Pickup
Range: 0.10 to 30.0 x In
Step: 0.1 x In.
TIME 50PH
50PH Time Delay
Range: 0.00 to 600.00 s.
Step: 0.01 s.
CNF
CONFIRM
OK
Validate the value selected.
The display and keypad handling for the other Instantaneous Overcurrent Functions
F50PL, F50NH
and
F50NL
are identical to the one just described.
In case of sensitive ground, the range for settings TAP 50NH/TAP 50NL is as follows:
Range: 0.005-0.12 A
Step: 0.001 A