RELAY COMMISSIONING
GEK-106273L
MIF Digital Feeder Protection
9-15
9.21.2. ADVANCED
SETTINGS
ENERVISTA MII
SETUP
HMI
USER
VALUE
RANGE
STEP
General Settings (Adv.)
GENERAL SET. ADV.
GENERAL
ADVANCED
Identification IDENTIFICATION ---
Text NA
Active Table
ACTIVE TABLE
TAB
1 – 2
NA
Trip Contact - Minimum
time closed.
TRIP MINIMUM TIME
TRIP MIN
TIME
50 – 300 ms.
1 ms.
Phase TOC (Table 2)
51P Function (Table
2)
F51P T2
51P Permission to Trip
51P Trip Permission
TRIP 51P T2
Y/N
NA
51P Tap / Pickup Value
51P Pickup T2
TAP 51P T2
0.1 – 2.4 In (Ph) 0.01 In (P)
51P Curve Type
51P Curve Type T2
CURV 51P T2
INV, V.I.,E.I.,
NA
51P Time Dial
51P Time Dial T2
DIAL 51P T2
0.05 – 2.00 (IEC)
0.01
0.5 – 20.0 (ANSI)
0.01
51P Definite Time Delay
51P Definite Time T2
TIME 51P T2
0 – 600.00 s.
0.01 s.
Ground TOC (Table 2)
51N Function (Table
2)
F51N T2
51N Permission to Trip
51N Trip Permission
TRIP 51N T2
Y/N
NA
51N Tap / Pickup (1/5 A
ground)
51N Pickup T2
TAP 51N T2
0.1 – 2.4 In
(Gnd)
0.01 In (G)
51N Tap / Pickup
(sensitive ground)
51N Pickup T2
TAP 51N T2
0.005-0.12 A
0.001 A
51N Curve Type
51N Curve Type T2
CURV 51N T2
INV, M.I.,E.I.,
NA
51N Time Dial
51N Time Dial T2
DIAL 51N T2
0.05 – 2.00 (IEC)
0.01
0.5 – 20.0 (ANSI)
0.01
51N Definite Time Delay
51N Definite Time T2
TIME 51N T2
0 – 600.00 s.
0.01 s.
Ph IOC High Set Table 2
50PH Function (Table
2)
F50PH T2
50PH Permission to Trip
50PH Trip Permission
TRIP 50PH T2
Y/N
NA
50PH Tap / Pickup
50PH Pickup T2
TAP 50PH T2
0.1 – 30 In (Ph) 0.1 In (Ph)
50PH Time Delay
50PH Time Delay T2
TIME 50PH T2
0 – 600.00 s.
0.01 s.
Ph IOC Low Set Table 2
50PL Function (Table
2)
F50PL T2
50PL Permission to Trip
50PL Trip Permission
TRIP 50PL T2
Y/N
NA
50PL Tap / Pickup
50PL Pickup T2
TAP 50PL T2
0.1 – 30 In (Ph) 0.1 In (Ph)
50PL Time Delay
50PL Time Delay T2
TIME 50PL T2
0 – 600.00 s.
0.01 s.
Gnd IOC High Set Table
2
50NH Funct. (Table 2)
F50NH T2
50NH Permission to Trip
50NH Trip Permission TRIP 50NH T2
Y/N
NA
50NH Tap / Pickup (1/5 A
ground)
50NH Pickup T2
TAP 50NH T2
0.1 – 30 In (Gnd)
0.1 In (G)
50NH Tap / Pickup
(sensitive ground)
50NH Pickup T2
TAP 50NH T2
0.005-0.12 A
0.001 A
50NH Time Delay
50NH Time Delay T2
TIME 50NH T2
0 – 600.00 s.
0.01 s.
Содержание GEK-106273L
Страница 19: ...GETTING STARTED 1 12 MIF Digital Feeder Protection GEK 106273L ...
Страница 95: ...SETTINGS 5 38 MIF Digital Feeder Protection GEK 106273L ...
Страница 101: ...I O CONFIGURATION 6 44 MIF Digital Feeder Protection GEK 106273L ...
Страница 127: ...KEYPAD AND DISPLAY 8 26 MIF Digital Feeder Protection GEK 106273L ...
Страница 147: ...INSTALLATION AND MAINTENANCE 10 2 MIF Digital Feeder Protection GEK 106273L ...
Страница 154: ...ANNEX 1 THERMAL IMAGE UNIT GEK 106273L MIF Digital Feeder Protection 11 7 Figure A 1 1 THERMAL CURVE FOR τ1 3 MINUTES ...
Страница 155: ...ANNEX 1 THERMAL IMAGE UNIT 11 8 MIF Digital Feeder Protection GEK 106273L Figure A 1 2 THERMAL CURVES FOR τ1 3 MIN ...
Страница 199: ...ANNEX 5 HARMONIC FILTERING 15 4 MIF Digital Feeder Protection GEK 106273L ...