B-78
F60 Feeder Protection System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
EB3A
PMU 1 df/dt Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB3B
PMU 1 df/dt Trigger Raise
0.1 to 15
Hz/s
0.01
F001
25
EB3C
PMU 1 df/dt Trigger Fall
0.1 to 15
Hz/s
0.01
F001
25
EB3D
PMU 1 df/dt Trigger Pkp Time
0 to 600
s
0.01
F001
10
EB3E
PMU 1 df/dt Trigger Dpo Time
0 to 600
s
0.01
F001
100
EB3F
PMU 1 df/dt Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EB45
PMU 1 df/dt Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB46
PMU 1 df/dt Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Power Trigger (Read/Write Setting)
EB88
PMU 1 Power Trigger Function
0 to 1
---
1
F102
0 (Disabled)
EB89
PMU 1 Power Trigger Active
0.25 to 3
pu
0.001
F001
1250
EB8A
PMU 1 Power Trigger Reactive
0.25 to 3
pu
0.001
F001
1250
EB8B
PMU 1 Power Trigger Apparent
0.25 to 3
pu
0.001
F001
1250
EB8C
PMU 1 Power Trigger Pkp Time
0 to 600
s
0.01
F001
10
EB8D
PMU 1 Power Trigger Dpo Time
0 to 600
s
0.01
F001
100
EB8E
PMU 1 Power Trigger Block (3 items)
0 to 4294967295
---
1
F300
0
EB94
PMU 1 Power Trigger Target
0 to 2
---
1
F109
0 (Self-reset)
EB95
PMU 1 Power Trigger Events
0 to 1
---
1
F102
0 (Disabled)
Phasor Measurement Unit Calibration (Read/Write Setting)
EBDC
PMU 1 Va Calibration Angle
-5 to 5
°
0.05
F002
0
EBDD
PMU 1 Va Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBDE
PMU 1 Vb Calibration Angle
-5 to 5
°
0.05
F002
0
EBDF
PMU 1 Vb Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBE0
PMU 1 Vc Calibration Angle
-5 to 5
°
0.05
F002
0
EBE1
PMU 1 Vc Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBE2
PMU 1 Vx Calibration Angle
-5 to 5
°
0.05
F002
0
EBE3
PMU 1 Vx Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBE4
PMU 1 Ia Calibration Angle
-5 to 5
°
0.05
F002
0
EBE5
PMU 1 Ia Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBE6
PMU 1 Ib Calibration Angle
-5 to 5
°
0.05
F002
0
EBE7
PMU 1 Ib Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBE8
PMU 1 Ic Calibration Angle
-5 to 5
°
0.05
F002
0
EBE9
PMU 1 Ic Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBEA
PMU 1 Ig Calibration Angle
-5 to 5
°
0.05
F002
0
EBEB
PMU 1 Ig Calibration Magnitude
95 to 105
%
0.1
F002
1000
EBEC
PMU 1 Sequence Voltage Shift Angle
-180 to 180
°
30
F002
0
EBED
PMU 1 Sequence Current Shift Angle
-180 to 180
°
30
F002
0
Phasor Measurement Unit Network Reporting Configuration (Read/Write Setting)
EC48
PMU Network Reporting Function
0 to 1
---
1
F102
0 (Disabled)
EC49
PMU Network Reporting ID Code
1 to 65534
---
1
F001
1
EC4A
PMU TCP Port Number
1 to 65535
---
1
F001
4712
EC4B
PMU UDP Port Number 1
1 to 65535
---
1
F001
4713
EC4C
PMU UDP Port Number 2
1 to 65535
---
1
F001
4714
Settings File Template (Read/Write Setting)
ED00
FlexLogic Displays Active
0 to 1
---
1
F102
1 (Enabled)
ED01
Template Access
---
---
---
F205
(none)
Setting File Template (Read Only Non-Volatile)
ED07
Last Settings Change Date
0 to 4294967295
---
1
F050
0
Settings File Template (Read/Write Setting)
ED09
Template Bitmask (750 items)
0 to 65535
---
1
F001
0
Phasor Measurement Unit Records (Read Only)
EFFF
PMU Recording Number of Triggers
0 to 65535
---
1
F001
0
Table B–10: MODBUS MEMORY MAP (Sheet 70 of 70)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание F60
Страница 10: ...x F60 Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 138: ...4 28 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 454: ...5 316 F60 Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 500: ...7 14 F60 Feeder Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 508: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 522: ...10 12 F60 Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 660: ...B 116 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 706: ...E 10 F60 Feeder Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 718: ...F 12 F60 Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 728: ...H 8 F60 Feeder Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 730: ...H 10 F60 Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...