![GE Grid Solutions F60 Скачать руководство пользователя страница 575](http://html.mh-extra.com/html/ge-grid-solutions/f60/f60_instruction-manual_571876575.webp)
GE Multilin
F60 Feeder Protection System
B-31
APPENDIX B
B.4 MEMORY MAPPING
B
4050
Flash Message Time
0.5 to 10
s
0.1
F001
10
4051
Default Message Timeout
10 to 900
s
1
F001
300
4052
Default Message Intensity
0 to 3
---
1
F101
0 (25%)
4053
Screen Saver Feature
0 to 1
---
1
F102
0 (Disabled)
4054
Screen Saver Wait Time
1 to 65535
min
1
F001
30
4055
Current Cutoff Level
0.002 to 0.02
pu
0.001
F001
20
4056
Voltage Cutoff Level
0.1 to 1
V
0.1
F001
10
Communications (Read/Write Setting)
407D
COM2 Selection
0 to 3
---
1
F601
0 (RS485)
407E
COM1 Minimum Response Time
0 to 1000
ms
10
F001
0
407F
COM2 Minimum Response Time
0 to 1000
ms
10
F001
0
4080
Modbus Slave Address
1 to 254
---
1
F001
254
4083
RS485 Com1 Baud Rate
0 to 11
---
1
F112
8 (115200)
4084
RS485 Com1 Parity
0 to 2
---
1
F113
0 (None)
4085
RS485 Com2 Baud Rate
0 to 11
---
1
F112
8 (115200)
4086
RS485 Com2 Parity
0 to 2
---
1
F113
2 (Even)
4087
Port 1 IP Address
0 to 4294967295
---
1
F003
2130706433
4089
Port 1 IP Subnet Mask
0 to 4294967295
---
1
F003
4278190080
408B
Port 1 Gateway IP Address
0 to 4294967295
---
1
F003
56554497
408D
Network Address NSAP
---
---
---
F074
0
4097
Port 1 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4098
Port 2 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
4099
Port 3 Link Loss Alert
0 to 1
---
1
F102
0 (Disabled)
409A
DNP Channel 1 Port
0 to 5
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 5
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
0 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
0 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
0 to 65535
---
1
F001
80
40A6
Main UDP Port Number for the TFTP Protocol
0 to 65535
---
1
F001
69
40A7
Data Transfer UDP Port Numbers for the TFTP Protocol
(zero means “automatic”) (2 items)
0 to 65535
---
1
F001
0
40A9
DNP Unsolicited Responses Function
0 to 1
---
1
F102
0 (Disabled)
40AA
DNP Unsolicited Responses Timeout
0 to 60
s
1
F001
5
40AB
DNP Unsolicited Responses Maximum Retries
1 to 255
---
1
F001
10
40AC
DNP Unsolicited Responses Destination Address
0 to 65519
---
1
F001
1
40AD
Ethernet Operation Mode
0 to 1
---
1
F192
1 (Full-Duplex)
40AE
DNP Current Scale Factor
0 to 8
---
1
F194
2 (1)
40AF
DNP Voltage Scale Factor
0 to 8
---
1
F194
2 (1)
40B0
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B1
DNP Energy Scale Factor
0 to 8
---
1
F194
2 (1)
40B2
DNP Power Scale Factor
0 to 8
---
1
F194
2 (1)
40B3
DNP Other Scale Factor
0 to 8
---
1
F194
2 (1)
40B4
DNP Current Default Deadband
0 to 100000000
---
1
F003
30000
40B6
DNP Voltage Default Deadband
0 to 100000000
---
1
F003
30000
40B8
DNP Power Default Deadband
0 to 100000000
---
1
F003
30000
40BA
DNP Energy Default Deadband
0 to 100000000
---
1
F003
30000
40BC
DNP Power Factor Default Deadband
0 to 100000000
--
1
F003
30000
40BE
DNP Other Default Deadband
0 to 100000000
---
1
F003
30000
40C0
DNP IIN Time Synchronization Bit Period
1 to 10080
min
1
F001
1440
40C1
DNP Message Fragment Size
30 to 2048
---
1
F001
240
40C2
DNP Client Address 3
0 to 4294967295
---
1
F003
0
40C4
DNP Client Address 4
0 to 4294967295
---
1
F003
0
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 70)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание F60
Страница 10: ...x F60 Feeder Protection System GE Multilin TABLE OF CONTENTS ...
Страница 30: ...1 20 F60 Feeder Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 138: ...4 28 F60 Feeder Protection System GE Multilin 4 2 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 454: ...5 316 F60 Feeder Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 500: ...7 14 F60 Feeder Protection System GE Multilin 7 1 COMMANDS 7 COMMANDS AND TARGETS 7 ...
Страница 508: ...8 8 F60 Feeder Protection System GE Multilin 8 2 FAULT LOCATOR 8 THEORY OF OPERATION 8 ...
Страница 522: ...10 12 F60 Feeder Protection System GE Multilin 10 6 DISPOSAL 10 MAINTENANCE 10 ...
Страница 660: ...B 116 F60 Feeder Protection System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 706: ...E 10 F60 Feeder Protection System GE Multilin E 1 IEC 60870 5 104 APPENDIX E E ...
Страница 718: ...F 12 F60 Feeder Protection System GE Multilin F 2 DNP POINT LISTS APPENDIX F F ...
Страница 728: ...H 8 F60 Feeder Protection System GE Multilin H 2 ABBREVIATIONS APPENDIX H H Z Impedance Zone ...
Страница 730: ...H 10 F60 Feeder Protection System GE Multilin H 3 WARRANTY APPENDIX H H ...