SVmco User Guidel
154
6.
With the hard disk selected in the tree view, select [Locate device] from
the right-click menu to cause the Alarm LED to blink at high speed (interval
of 0.3 seconds).
7.
Confirm the hard disk location. Then, with the hard disk selected in the
tree view, select [Stop location] from the right-click menu to turn off the
Alarm LED.
8.
With the hard disk selected in the tree view, select [Make Offline] from
the right-click menu to turn on the Alarm LED.
9.
Confirm that [Status] for the target hard disk is [Failed], [Offline], or
[Available].
* A field engineer performs steps 10 to 12 as the hard disk recovery
procedure.
10.
Confirm that the Alarm LED of the hard disk on the main unit of the
server is on.
11.
Replace the hard disk whose Alarm LED is on.
12.
In the SVOM Web-UI, open the window for the partition. Select [Driver
Monitor] from the left menu. The window displays "Error" or "Warning" at
[Status] for the array controller card that manages the faulty hard disk.
Select the card. Then, click the [Acknowledge] button.