154
000761AG-F
8 - Maintenance
- Error code
- Error message
- Warning
Name of Alarm and Cause
Solution
E053
- AFDD Fault
-
Yellow LED
Arc Fault board autotest failed:
Problem detected during the AFDD board autotest
phase.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E054
- AFDD comm. Fault
-
Yellow LED
Arc Fault board communication error:
Error on the RS485 serial communication detected
between the inverter and the AFDD board.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E055
- AFDD wrong conf.
-
Yellow LED
Arc Fault board parameter reading error:
Error in the parameter reading by the system.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E056
- Over Temp. (from
external box)
-
Yellow LED
Excessive temperature measured inside the inver-
ter's wiring box:
High internal temperature.
This error relates to the temperature measured on
external boxes (e.g.:TRIO-20.0/27.6kW).
• Check that the inverter is not exposed to direct sunlight. Wait
for the temperatures to which the inverter is exposed to return
to the operating range and for the inverter to cool down.
- If the problem persists (once the ambient temperature has
returned to within the range), contact customer assistance.
Remember to wait the time needed to allow the inverter to
cool down
E057
- Vbulk reading error
-
Yellow LED
Input voltage (Vin) higher than booster voltage
(Vbulk):
The error occurs if the input voltage exceeds the
Bulk voltage (voltage on the DC-DC circuit inside the
inverter)
• It is necessary to measure the input voltage inside the inver-
ter with a voltmeter.
- If it is higher than the maximum voltage of the operating
range, the alarm is genuine and it is necessary to check the
configuration of the PV generator. If the voltage has also
exceeded the maximum input threshold the inverter could be
damaged.
- If it is lower than the maximum voltage of the operating
range, the alarm is caused by an internal malfunction and it is
necessary to contact customer assistance.
E058
- Pin vs Pout check
error
-
Yellow LED
Error in the check of Pin vs Pout:
The error occurs if the difference between the measu-
red value of input power and that of output power is
greater than the limit imposed internally to the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E065
- Stop Button
-
Yellow LED
Emergency (stop) button activated:
This code marks the activation of the emergency
button (button pressed). This warning is activated only
where there is DC or AC voltage as, if the emergency
button is pressed while it is operating only by battery,
it causes the whole system to shut down.
• Check that the emergency button has been pressed and if
necessary deactivate it.
- If the warning persists even though the button has been
deactivated, contact customer assistance.
E066
- Charger-Bulk
-
Yellow LED
Error in the “Charger” circuit:
Error internal to inverter relating to the bulk voltage of
the circuit linked to battery charger
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E067
- Charger - OV
-
Yellow LED
Overvoltage of "battery charger" ("Charger"
circuit):
Error inside the inverter. The alarm is raised when
the battery charger voltage exceeds the overvoltage
threshold (internal unchangeable threshold).
• The error might continue when the battery is disconnected
(e.g. activation of emergency button).
• If the message persists and is not linked to the battery being
disconnected, contact customer assistance.
E068
- Charger - OC
-
Yellow LED
Overcurrent of "battery charger" ("Charger"
circuit):
Error inside the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E069
- Charger-SlowRamp
-
Yellow LED
Error internal to inverter linked to the battery pack
charger circuit ("Charger" circuit"):
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E070
- Charger-preChar.
-
Yellow LED
Error inside the inverter.
• Error inside the inverter probably linked to the fuse in the
damaged battery pack; the error cannot be verified externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E074
- Internal error
-
Yellow LED
Communication error inside the inverter:
The alarm occurs when there are communication pro-
blems between the control devices inside the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E077
- Internal Error
-
Yellow LED
Error in the system configuration:
Error inside the inverter
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E078
- Riso Test fail
-
Yellow LED
Riso test error:
Problem detected during the Riso test phase.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.