113
000877BG-F
7 - Operation
SETTING section
In the
SETUP
section it’s possible to access the following sub-menus:
• AC output Rating (Only visible with Admin Plus privileges)
• AC Settings (Only visible with Admin Plus privileges)
• Active Power Control (Only visible with Admin Plus privileges)
• DC Settings
• Digital Inputs
• Frequency Control: P(f) (Only visible with Admin Plus privileges)
• Ramp Control (Only visible with Admin Plus privileges)
• Reactive Power Control (Only visible with Admin Plus privileges)
AC output Rating (Only visible and editable with Admin
Plus privileges)
In the
AC output Rating
sub-menu you can config the output power
limitation by changing the Maximum AC output power and the maxi-
mum apparent output power parameters.
Do not change these parameters if not requested by the grid operator.
AC Settings (Only visible and editable with Admin Plus
privileges)
In the
AC Settings
sub-menu you can setup the parameter related to
the Output AC side:
Changing the above-mentioned parameters may prevent disconnection from the grid if the
new values exceed those given in the standards of the country of installation. If these parame-
ters are changed to values outside the standard range, an interface protection must be instal-
led external to the inverter in accordance with the requirements of the country of installation.
1. Grid Connection
By editing these settings it’s possible to change the grid connection
thresholds parameters to which the inverter have to connect to the grid
2. Grid Prote VRT/FRT
By editing these settings it’s possible to enable/disable and change the
grid protection intervention thresholds parameters. In addition it is pos-
sible to change voltage ride thorough (HVRT, LVRT) and frequency ride
thorough (HFRT, LFRT) settings.