7 - Operation
For the configurable relay operating mode “Alarm Conf.”, the following considerations are
valid:
If the alarm condition is persistent, the alarm contact cyclically switches from its resting state
to its activated state.
In the presence of W002 signalling (Input UV – input voltage below the limit of operation),
the alarm contact switches to then reset itself at the end of the alarm signal. This means that
during the reduced input voltage (display message “Waiting Sun”) the alarm contact remains
in its resting position.
In the presence of W003, W004, W005, W006, W007 signalling, the alarm contact switches
to then reset itself at the end of the alarm signal. This means that during the absence of grid
voltage (display message “Missing Grid”) the alarm contact remains in its resting position.
• Alarm-Contact (crepuscolar):
The relay is activated (status: switched) as soon as the inverter input
voltage exceeds the activation voltage set.
The relay switch to rest position when the input voltage drops below 70%
of the activation voltage set.
This mode is useful for disconnecting any output transformers that could
have unnecessary consumption during the night.
• Alarm-Contact (alarm ALL - latch):
The relay is activated (status: switched) whenever an error (code Exxx)
or a warning (code Wxxx) is present. When the inverter returns to the
normal operating state and reconnects with the grid, the contact returns
to its position of rest.
Selectable alarms for which the relay is activated
E001
E002
E003
E004
E005
E006
E007
E010
E011
E013
E014
E015
E017
E018
E019
E020
E021
E022
E023
E025
E029
E031
E032
E033
E034
E036
E037
E053
E055
E075
E077
E078
E079
E080
E084
W002
W004
W005
W006
W007
W011
W015
W017
W046
W047
W048
If the alarm condition is persistent, the relay will remain activated (sta-
tus:switched)
Vin > Vstart
Vin < Vstart
GRID RECONNECTION
t=based on Country Standard
Vin
IS STILL LESS THAN
Vstart
Yes
No
N.C.
N.O.
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State: Switched
Relay State:
Idle
INVERTER RUN
ERROR OCCURENCY
ERROR MESSAGE
t=15s
GRID RECONNECTION
t=based on Country Standard
ERROR
STILL
PRESENT
Yes
No
N.C.
N.O.
N.C.
N.O.
Relay State:
Idle
Relay State: Switched
N.C.
N.O.
Relay State: Switched