8 - Maintenance
Power limitation messages
The equipment can signal possible output power limitations which may
occur on the basis of:
- settings made by the user
- settings required by the grid standard of the country of installation
- protective devices inside the inverter
The signals and the messages can only be verified using the internal
Webserver.
The following table gives the complete list of power limitation messages relating to string
inverters.
Some messages may not be used depending on the inverter model installed.
- Message on di-
splay
- Signal
Name of Derating and Cause
Solution
- LIMxxx% CODE:00
Power limitation:
The message indicates that the user has set an output power
limitation for the inverter.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• Check the limitation value in “Settings > Power
Reduction”.
- LIMxxx% CODE:01
Power limitation for over-frequency:
The message indicates that the user has set a power limitation
due to over frequency in order to reduce the maximum output po-
wer of the inverter when the grid frequency exceeds certain limits.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• Check the limitation value set in “Settings > Servi-
ce Power > OF Derating”
- LIMxxx% CODE:02
Power limitation for over-voltage:
The message indicates that the user has set a power limitation due
to overvoltage (parameter U >(10 min)) in order to reduce the maxi-
mum output power of the inverter when the reading of the average
grid voltage exceeds certain limits.
The sampling of readings is done every 10 minutes (U>(10min)).
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• Check the limitation value in “Settings > Service
Power > U>(10min) Der.”
- LIMxxx% CODE:03
Anti-islanding power limitation:
The message indicates that a power limitation is active since an
"islanding" condition has been recorded.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• If the inverter remains connected to the grid and
the limitation is active, contact customer assistance
- LIMxxx% CODE:04
Power limitation due to low grid voltage:
The message indicates that an output power limitation may occur
since a low grid voltage (AC) condition has been recorded.
LIM xxx% = Power reduction percentage
Examples:
LIM 100% = no power limitation
LIM 50% = limitation to 50% of the output nominal power
• Check that the grid voltage is lower than the mini-
mal voltage. Should this condition persist, contact
the grid operator to resolve the problem.