ID ISC.MR200
FEIG ELECTRONIC GmbH
Page 65 of 144
H40801-5e-ID-B.doc
EN:
b0:
disabled
b1:
enabled
KEEP-ALIVE-TIME:
Defines the cycle time for keep alive notification.
max. time period
KEEP-ALIVE-TIME
10...65535 * 1s
DEST-IP-ADDRESS:
Defines the destination IP address.
DEST-IP-PORT-NUMBER:
Defines the destination port number.
HOLD-TIME:
Defines the hold time of the TCP/IP connection after sent of a notification. The time will be
retriggered with every new notification
Notes:
Notification Mode is only available from hardware version FE556/4 or higher.
For every change in the CFG’s 40-45 and CFG 49 a system reset 0x64 is necessary for
the LAN Controller in order to send the values to the LAN Controller. It is important to
first write all the values to the EEPROM and only then carry out a system reset.
The system reset is always replied to with a Status OK, even if sending the values to
the LAN Controller has failed. The LAN Controller retains its old values in cases of er-
ror.
If the system reset 0x64 is performed using the RS232 port, then the LAN Controller
will be initialized with the new values approx. 1 min. after the status message.
If the TCP/IP connection is used for the system reset 0x64, then following the status
message the LED’s V3 (Input) and V4 (Output) will come on for approx. 1 min. Once the
LED’s turn off the LAN Controller initializes the new values approx. 1 min. later.
The configuration pages CFG40-49 cannot be set to default using the command 0x83
Reset.