Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
82
Hauser
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Sensor range (SENSOR_
RANGE)
Read only
(EU_100, EU_0)
OOS
(UNITS_INDEX,
DECIMAL)
Physical measuring range of the sensor:
EU_100 (upper sensor range limit)
EU_0 (lower sensor range limit)
UNITS_INDEX (unit of the SENSOR_VALUE)
DECIMAL (number of decimal places for the
SENSOR_VALUE. This does not affect the measured value
display.)
Sensor offset (SENSOR_
OFFSET)
OOS
Offset of the SENSOR_VALUE
The following values are permitted:
• -10 to +10 for Celsius, Kelvin, mV and Ohm
• -18 to +18 for Fahrenheit, Rankine
2-wire compensation
(TWO_WIRE_
COMPENSATION)
OOS
Two-wire compensation
The following values are permitted:
0 to 30 Ω
Sensor serial number
(SENSOR_SN)
AUTO - OOS
Sensor serial number
Sensor max. indicator
(SENSOR_MAX_ INDICATOR)
AUTO - OOS
Max. indicator of the SENSOR_VALUE
Is stored in the non-volatile memory in intervals of 10
minutes. Can be reset.
Sensor min. indicator
SENSOR_MIN_ INDICATOR
AUTO - OOS
Min. indicator of the SENSOR_VALUE
Is stored in the non-volatile memory in intervals of 10
minutes. Can be reset.
Mains filter (MAINS_FILTER)
OOS
Mains filter for the A/D converter
Calibration highest point
(CAL_POINT_HI)
OOS
Upper point for linear characteristic calibration (this
affects offset and slope).
To be able to write this parameter,
"SENSOR_CAL_METHOD" must be set to "User trim
standard calibration".
Calibration lowest point
(CAL_POINT_LO)
OOS
Lower point for linear characteristic calibration (this
affects offset and slope).
To be able to write this parameter,
"SENSOR_CAL_METHOD" must be set to "User trim
standard calibration".
Calibration minimum span
(CAL_MIN_SPAN)
OOS
Span of the measurement range, depending on the
configured sensor type.
Calibration unit (CAL_UNIT)
Read only
Unit for sensor calibration.
Sensor calibration method
(SENSOR_CAL_ METHOD)
OOS
Factory trim standard calibration:
Sensor linearization with the factory calibration values
User trim standard calibration:
Sensor linearization with the values CAL_POINT_HI and
CAL_POINT_LO
The original linearization can be restored by
resetting this parameter to "Factory trim standard
calibration". The Transducer Block makes a wizard
available (User Sensor Trim) for linear characteristic
calibration.
Sensor calibration location
(SENSOR_CAL_ LOC)
AUTO - OOS
Name of the location where the sensor calibration was
performed.
Sensor calibration date
(SENSOR_CAL_ DATE)
AUTO - OOS
Date and time of the calibration.
Sensor calibration who
(SENSOR_CAL_ WHO)
AUTO - OOS
Name of the person responsible for the calibration.