Commissioning
iTEMP TMT85
36
Hauser
System configuration / connecting function blocks:
19.
A0042922
A final "overall system configuration" is necessary so that the operating mode of the
Analog Input function block can be set to AUTO and the field device is integrated into
the system application. For this purpose, configuration software, e.g. NI-FBUS
Configurator from National Instruments, is used to connect the function blocks to the
desired control strategy (generally graphically) and then the time for processing the
individual process control functions is specified.
20. Once you have specified the active LAS (), download all the data and parameters to
the field device.
21. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to
AUTO.
This is only possible if the following two conditions are met:
– The function blocks are correctly connected to one another.
– The Resource Block is in the AUTO operating mode.