Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
84
Hauser
14.3.8 Transducer Block "Advanced Diagnostic"
The "Advanced Diagnostic" Transducer Block is used to configure and display all the
diagnostic functions of the transmitter.
Functions such as
• Corrosion detection
• Drift detection
• Ambient temperature monitoring
are displayed here.
Corrosion monitoring
Sensor connection cable corrosion can lead to false measured value readings. Therefore
the unit offers the possibility of detecting corrosion before a measured value is affected.
Corrosion monitoring is only possible for RTDs with a 4-wire connection and
thermocouples (see also → 43).
Drift detection can be configured with the SENSOR_DRIFT_MONITORING parameter. Drift
detection can be enabled or disabled. If drift detection is enabled and a drift occurs, an
error or maintenance request is generated. A distinction is made between 2 specific modes
(SENSOR_ DRIFT_MODE). In the 'Overshooting' mode, a status message is generated if the
limit value (SENSOR_DRIFT_ALERT_VALUE) for the drift is overshot, or if the limit value
is undershot in the 'Undershooting' mode.
A0042928
22
Drift detection
A
'Undershooting' mode
B
'Overshooting' mode
D
Drift
L+,
L-
Upper (+) or lower (-) limit value
t
Time
x
Error or request for maintenance, depending on the setting