iTEMP TMT85
Diagnostics and troubleshooting
Hauser
41
Category
No.
Status messages
•
ACTUAL_STAT
US_NUMBER
in the
'Advanced
Diagnostics'
Transducer
Block
•
Local display
Error messages in the
relevant Sensor
Transducer Block
Sensor
Transducer Block
measured value
status (default)
Cause of error /
remedy
Output variables
affected
F-
437
Device status
message (FF):
Configuration
incorrect
F-437
Local display:
F437
BLOCK_ERR = Other |
Block configuration
error
QUALITY = BAD
Cause of error:
Incorrect
configuration in
Transducer Blocks
"Sensor 1 and 2".
The reason for the
configuration error
is displayed in the
"BLOCK_ERR_DES
C1" parameter.
Remedy:
Check the
configuration of
the sensor types
used, the units and
the settings of PV1
and/or PV2.
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
Configuration error
SUBSTATUS =
Device failure
9.2.2
Category M diagnostics messages
Category
No.
Status messages
•
ACTUAL_STAT
US_NUMBER
in the
'Advanced
Diagnostics'
Transducer
Block
•
Local display
Error messages in the
relevant Sensor
Transducer Block
Sensor
Transducer Block
measured value
status (default)
Cause of error /
remedy
Output variables
affected
M-
042
Device status
message (FF):
Corrosion
M-042
Local display:
M042 ↔
Measured value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN
(configurable)
Cause of error:
Corrosion detected
on the sensor
terminals.
Remedy:
Check wiring and
replace if
necessary.
SV1, SV2, also
PV1, PV2
depending on the
configuration
Transducer_Error = No
error
SUBSTATUS =
Sensor conversion
not accurate
M-
101
Device status
message (FF):
Sensor value too
low
M-101
Local display:
M101 ↔
Measured value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN
Cause of error:
Physical
measuring range
undershot.
Remedy:
Select suitable
sensor type.
SV1, SV2, also
PV1, PV2
depending on the
configuration
Transducer_Error = No
error
SUBSTATUS =
Sensor conversion
not accurate
M-
102
Device status
message (FF):
Sensor value too
high
M-102
Local display:
M102 ↔
Measured value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN
Cause of error:
Physical
measuring range
overshot.
Remedy:
Select suitable
sensor type.
SV1, SV2, also
PV1, PV2
depending on the
configuration
Transducer_Error = No
error
SUBSTATUS =
Sensor conversion
not accurate