Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
88
Hauser
Parameter
Write access with
operating mode
(MODE_BLK)
Description
Display source x
DISP_SOURCE_X
AUTO - OOS
Use this function to select the value to be displayed. Possible
settings:
• Off
• Primary Value 1
• Sensor Value 1
• Primary Value 2
• Sensor Value 2
• Device temperature
If all 3 display channels are switched off ('Off' option),
the value for primary value 1 automatically appears on
the display. If this value is not available (e.g. 'No
Sensor' option selected in the Sensor Transducer Block
1, 'SENSOR_TYPE' parameter), primary value 2 is
displayed.
Display value description x
DISP_VALUE_X_DESC
AUTO - OOS
Description of value displayed.
Maximum 12 letters. The value is not shown on the
display.
Decimal places x
DISP_VALUE_ X_FORMAT
AUTO - OOS
Use this function to select the number of decimal places
displayed.
Choose between 0 and 4. The option 4 'AUTO' means that
the maximum possible number of decimal places will always
appear on the display.
Possible settings:
• Auto
• xxxxx
• xxxx.x
• xxx.xx
• xx.xxx
Example of parameterization:
The following measured values should be shown on the display:
Value 1:
Measured value to be displayed:
Primary Value of Sensor Transducer 1 (PV1)
Measured value unit:
° C
Decimal places:
2
Value 2:
Measured value to be displayed:
DEVTEMP_VALUE
Measured value unit:
° C
Decimal places:
1
Value 3:
Measured value to be displayed:
Sensor Value (measured value) of Sensor Transducer 2 (SV2)
Measured value unit:
° C
Decimal places:
2
Every measured value should be visible on the display for 12 seconds.