Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
86
Hauser
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Actual Status Number /
Previous Status Number
(ACTUAL_ STATUS_
NUMBER / PREVIOUS_
STATUS_ NUMBER)
Read only /
AUTO - OOS
Current/previous status number:
000 NO_ERROR: No error is present
041 SENSOR_BREAK: Sensor break
043 SENSOR_SHORTCUT: Sensor short-circuit
042 SENSOR_CORROSION: Corrosion of terminals or sensor
cables
101 SENSOR_UNDERUSAGE: Sensor measured value is below
the linearization range
102 SENSOR_OVERUSAGE: Sensor measured value is above
the linearization range
104 BACKUP_ACTIVATED: Backup function activated due to
sensor failure
103 DEVIATION: Sensor drift detected
501 DEVICE_PRESET: Reset routine in progress
482 SIMULATION: Device is in the simulation mode
402 STARTUP: Device is in the startup/initialization phase
502 LINEARIZATION: Linearization incorrectly selected or
configured
901 AMBIENT_TEMPERATUR_LOW: Ambient temperature
too low; DEVTEMP_VALUE < –40 °C (–40 °F)
902 AMBIENT_TEMPERATURE_HIGH: Ambient temperature
too high; DEVTEMP_VALUE > 85 °C (185 °F)
261 ELECTRONICBOARD: Electronics module/hardware
faulty
431 NO_CALIBRATION: Calibration values lost/modified 283
MEMORY_ERROR: Contents of memory inconsistent
221 RJ_ERROR: Error in reference junction measurement/
internal temperature measurement
Actual Status Channel /
Previous Status Channel
(PREVIOUS/ ACTUAL_
STATUS_ CHANNEL)
Read only /
AUTO - OOS
ACTUAL_STATUS_CHANNEL displays the channel that
currently has the error with the highest value.
PREVIOUS_STATUS_CHANNEL indicates the channel where
an error last occurred.
Actual Status Description /
Previous Status Description
(PREVIOUS/ ACTUAL_
STATUS_DESC)
Read only /
AUTO - OOS
Displays the descriptions of the current and previous error
status.
The descriptions can be taken from the description for
the Actual Status Number/ Previous Status Number
parameter.
Actual Status Count
(ACTUAL_ STATUS_
COUNT)
Read only
The number of status messages currently active in the device.
Primary Value 1 Max.
Indicator PV1_MAX_
INDICATOR
AUTO - OOS
Indicator for the maximum value to occur for PV1, can be
reset by writing any value in this parameter.
Primary Value 1 Min.
Indicator PV1_MIN_
INDICATOR
AUTO - OOS
Indicator for the minimum value to occur for PV1, can be
reset by writing any value in this parameter.
Primary Value 2 Max.
Indicator PV2_MAX_
INDICATOR
AUTO - OOS
Indicator for the maximum value to occur for PV2, can be
reset by writing any value in this parameter.
Primary Value 2 Min.
Indicator PV2_MIN_
INDICATOR
AUTO - OOS
Indicator for the minimum value to occur for PV2, can be
reset by writing any value in this parameter.
Sensor 1 Max. Indicator
SV1_MAX_ INDICATOR
AUTO - OOS
Indicator for the maximum value to occur at sensor 1, can be
reset by writing any value in this parameter.
Sensor 1 Min. Indicator
SV1_MIN_ INDICATOR
AUTO - OOS
Indicator for the minimum value to occur at sensor 1, can be
reset by writing any value in this parameter.
Sensor 2 Max. Indicator
SV2_MAX_ INDICATOR
AUTO - OOS
Indicator for the maximum value to occur at sensor 2, can be
reset by writing any value in this parameter.