iTEMP TMT85
Operation via FOUNDATION Fieldbus
TM
Hauser
69
Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
33
Confirm Time
(CONFIRM_TIME)
AUTO - OOS
Specify the confirmation time for the event report. If the device does not
receive confirmation within this time, the event report is sent to the fieldbus
host system again.
Factory setting:
640000 1/32 ms
20
Cycle Selection (CYCLE_SEL)
AUTO - OOS
Displays the block execution method used by the fieldbus host system.
The block execution method is selected by the fieldbus host system.
19
Cycle Type (CYCLE_TYPE)
Read only
Displays the block execution methods supported by the device.
Display:
SCHEDULED
Scheduled block execution method
BLOCK EXECUTION
Sequential block execution method
MANUF SPECIFIC
Manufacturer-specific
9
DD Resource (DD_RESOURCE)
Read only
Displays the source for the device description in the device.
Display:
(blank spaces)
13
DD Revision (DD_REV)
Read only
Displays the revision number of the ITK-tested device description.
12
Device Revision (DEV_REV)
Read only
Displays the revision number of the device.
45
Device Tag (DEVICE_TAG)
Read only
Tag name/device TAG.
11
Device Type (DEV_TYPE)
Read only
Displays the device ID number in hexadecimal format.
Display:
0x10CE (hex) for TMT85
44
Electronic Name Plate Version
(ENP_VERSION)
Read only
Version of the ENP (electronic name plate).
28
Fault State (FAULT_STATE)
Read only
Current status display of the fault state of the Analog Output and Discrete
Output function blocks.
54
Check Active
(FD_CHECK_ACTIVE)
Read only
Indicates whether a diagnostic event of the defined category is currently
pending.
66
Check Alarm (FD_CHECK_ALM) AUTO - OOS
Alarms that are actively transmitted by the device to the fieldbus.
58
Check Map (FD_CHECK_MAP)
AUTO - OOS
Enable or disable diagnostic events or diagnostic groups for the relevant
category.
62
Check Mask
(FD_CHECK_MASK)
AUTO - OOS
Disables the transmission of device messages to the fieldbus.
70
Check Priority (FD_CHECK_PRI) AUTO - OOS
Indicates the alarm priority of the alarm transmitted to the fieldbus.
51
Fail Active (FD_FAIL_ACTIVE)
Read only
Indicates whether a diagnostic event of the defined category is currently
pending.
63
Fail Diagnostic Alarm
(FD_FAIL_ALM)
AUTO - OOS
Alarms that are actively transmitted by the device to the fieldbus.
55
Fail Map (FD_FAIL_MAP)
AUTO - OOS
Enable or disable diagnostic events or diagnostic groups for the relevant
category.
59
Fail Mask (FD_FAIL_MASK)
AUTO - OOS
Disables the transmission of device messages to the fieldbus.
67
Fail Priority (FD_FAIL_PRI)
AUTO - OOS
Indicates the alarm priority of the alarm transmitted to the fieldbus.
53
Maintenance Active
(FD_MAINT_ACTIVE)
Read only
Indicates whether a diagnostic event of the defined category is currently
pending.
65
Maintenance Alarm
(FD_MAINT_ALM)
AUTO - OOS
Alarms that are actively transmitted by the device to the fieldbus.
57
Maintenance Map
(FD_MAINT_MAP)
AUTO - OOS
Enable or disable diagnostic events or diagnostic groups for the relevant
category.