Technical data
iTEMP TMT85
60
Hauser
Designation
Standard
Long-term drift (±)
Type K (36)
≤ 0.09 °C (0.162 °F) + 0.017% *
(MV + 150 °C (270 °F))
≤ 0.14 °C (0.252 °F) + 0.023% *
measuring span
≤ 0.19 °C (0.342 °F) + 0.024% *
measuring span
Type N (37)
IEC 60584-1
≤ 0.13 °C (0.234 °F) + 0.015% *
(MV + 150 °C (270 °F))
≤ 0.2 °C (0.36 °F) + 0.02% *
measuring span
≤ 0.28 °C (0.5 °F) + 0.02% *
measuring span
Type R (38)
≤ 0.31 °C (0.558 °F) + 0.011% *
(MV - 50 °C (90 °F))
≤ 0.5 °C (0.9 °F) + 0.013% *
measuring span
≤ 0.69 °C (1.241 °F) + 0.011% *
measuring span
Type S (39)
IEC 60584-1
≤ 0.31 °C (0.558 °F) + 0.011% *
measuring span
≤ 0.5 °C (0.9 °F) + 0.013% *
measuring span
≤ 0.7 °C (1.259 °F) + 0.011% *
measuring span
Type T (40)
≤ 0.09 °C (0.162 °F) + 0.011% *
measuring span
≤ 0.15 °C (0.27 °F) + 0.013% *
measuring span
≤ 0.2 °C (0.36 °F) + 0.012% *
measuring span
Type L (41)
≤ 0.06 °C (0.108 °F) + 0.017% *
measuring span
≤ 0.1 °C (0.18 °F) + 0.022% *
measuring span
≤ 0.14 °C (0.252 °F) + 0.022% *
measuring span
Type U (42)
≤ 0.09 °C (0.162 °F) + 0.013% *
measuring span
≤ 0.14 °C (0.252 °F) + 0.017% *
measuring span
≤ 0.2 °C (0.360 °F) + 0.015% *
measuring span
Type L (43)
GOST R8.585-2001
≤ 0.08 °C (0.144 °F) + 0.015% *
measuring span
≤ 0.12 °C (0.216 °F) + 0.02% *
measuring span
≤ 0.17 °C (0.306 °F) + 0.02% *
measuring span
Voltage transmitter (mV)
–20 to 100 mV
-
≤ 2 µV + 0.022% * measuring
span
≤ 3.5 µV + 0.03% * measuring
span
≤ 4.7 µV + 0.033% * measuring
span
Influence of reference
junction
Pt100 DIN IEC 60751 Cl. B (internal reference junction with thermocouples TC)
13.5 Environment
Ambient temperature
range
–40 to +85 °C (–40 to +185 °F), for hazardous areas see Ex documentation → 64
Storage temperature
–40 to +100 °C (–40 to +212 °F)
Altitude
Up to 4000 m (4374.5 yards) above sea level
Humidity
• Condensation permitted as per IEC 60 068-2-33
• Max. rel. humidity: 95% as per IEC 60068-2-30
Climate class
C as per EN 60654-1
Degree of protection
• Head transmitter with screw terminals: IP 00, with spring terminals: IP 30. In installed
state, depends on the terminal head or field housing used.
• When installing in field housing TA30A, TA30D or TA30H: IP 66/67 (NEMA Type 4x
encl.)
Shock and vibration
resistance
Vibration resistance as per IEC 60068-2-6
10 to 2
000 Hz at 5g (increased vibration stress)
Electromagnetic
compatibility (EMC)
CE compliance