Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
10
Manufacturer ID
(MANUFAC_ID)
Read only
Displays the manufacturer's ID number.
Display:
0x452B48 (hex) = Hauser
31
Max Notify (MAX_NOTIFY)
Read only
Displays the maximum number of event reports supported by the device that
can simultaneously exist as unconfirmed reports.
Display:
4
22
Memory Size (MEMORY_SIZE)
Read only
Displays the available configuration memory in kilobytes.
This parameter is not supported.
21
Minimum Cycle Time
(MIN_CYCLE_T)
Read only
Displays the min. execution time.
5
Block Mode (MODE_BLK)
AUTO - OOS
Displays the actual and target operating mode of the Resource Block, the
permitted modes which the Resource Block supports and the normal
operating mode.
Display:
AUTO - OOS
The Resource Block supports the following operating modes:
• AUTO (automatic mode)
The execution of the remaining blocks (ISEL, AI and PID function
block) is permitted in this operating mode.
• OOS, (Out of Service)
The block is in the “Out of Service” mode. The execution of the
remaining blocks (ISEL, AI and PID function block) is stopped in this
operating mode. These blocks cannot be set to the AUTO mode.
The current operating status of the Resource Block is also shown via
the RS_STATE parameter.
50
Resource Directory
(RES_DIRECTORY)
Read only
Displays the Resource Directory for the electronic name plate (ENP).
23
Nonvolatile Cycle Time
(NV_CYCLE_T)
Read only
Displays the time interval in which the dynamic device parameters are stored
in the nonvolatile memory.
The time interval displayed refers to the storage of the following dynamic
device parameters:
• OUT
• PV
• FIELD_VAL
• SP
These values are stored in the nonvolatile memory every 11 minutes.
Display: 21120000 (1/32 ms).
49
Order Code / Identification
(ORDER_CODE)
Read only
Displays the order code for the device.
47
Extended order code
(ORDER_CODE_EXT)
Read only
Displays the extended order code of the device.
48
Extended order code part2
(ORDER_CODE_ EXT_PART2)
Read only
Displays the second part of the extended order code. This is always empty in
the case of this device, which is why this parameter does not appear in some
host systems.