Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
72
Hauser
Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
16
Restart (RESTART)
AUTO - OOS
The device can be reset in a variety of ways via this parameter.
Options:
• Restart UNINITIALIZED
• RUN
• Restart RESOURCE (restart the Resource Block)
• Restart with DEFAULTS (restart with the defined default values according
to FFSpec. (only FF bus parameters))
• Restart PROCESSOR (restart the processor)
• Restart Factory (resets all the device parameters to the default values)
• Restart Order Configuration (resets all the device parameters to the order
configuration)
• Restart Default Blocks (resets the blocks to the order configuration, e.g.
pre-instantiatied blocks)
7
Resource State (RS_STATE)
Read only
Displays the current operating status of the Resource Block.
Display:
STANDBY
The Resource Block is in the OOS operating mode. The remaining blocks
cannot be executed.
ONLINE LINKING
The configured connections between the function blocks are not yet
established.
ONLINE
Normal operating mode, the Resource Block is in the AUTO operating mode.
The configured connections between the function blocks have been
established.
46
Serial Number
(SERIAL_NUMBER)
Read only
Displays the device serial number.
29
Set Fault State (SET_FSTATE)
AUTO - OOS
The fault state can be activated manually via this parameter.
26
Shed Remote Cascade
(SHED_RCAS)
AUTO - OOS
Specify the monitoring time for checking the connection between the
fieldbus host system and a function block in the RCAS operating mode. Once
the monitoring time elapses, the function block switches from the RCAS
operating mode to the operating mode selected in the SHED_OPT parameter.
Factory setting:
640000 1/32 ms
27
Shed Remote Out (SHED_ROUT) AUTO - OOS
Specify the monitoring time for checking the connection between the
fieldbus host system and the PID function block in the ROUT operating mode.
Once the monitoring time elapses, the PID function block switches from the
ROUT operating mode to the operating mode selected in the SHED_OPT
parameter. A detailed description of the PID function block is provided in the
FOUNDATION Fieldbus
TM
Function Block Manual on the CD-ROM provided
(BA00062S/04).
Factory setting:
640000 1/32 ms
3
Strategy (STRATEGY)
AUTO - OOS
Parameter for grouping the blocks, thereby enabling faster evaluation.
Grouping is performed by entering the same numerical value in the
STRATEGY parameter of each individual block.
Factory setting:
0
These data are neither checked nor processed by the Resource Block.
1
Static Revision (ST_REV)
Read only
Displays the revision status of the static data.
The revision status is incremented each time the static data change.
2
Tag Description (TAG_DESC)
AUTO - OOS
Use this function to enter a user-specific text for the clear identification and
assignment of the block.
8
Test Read Write (TEST_RW)
AUTO - OOS
This parameter is required only for interoperability tests and has no
significance in normal operation.