iTEMP TMT85
Operation via FOUNDATION Fieldbus
TM
Hauser
87
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Sensor 2 Min. Indicator
SV2_MIN_ INDICATOR
AUTO - OOS
Indicator for the minimum value to occur at sensor 2, can be
reset by writing any value in this parameter.
Device Temperature Max.
Indicator DEVTEMP_ MAX_
INDICATOR
AUTO - OOS
Indicator for the maximum value to occur at the internal
reference temperature measuring point, can be reset by
writing any value in this parameter.
Device Temperature Min.
Indicator DEVTEMP_MIN_
INDICATOR
AUTO - OOS
Indicator for the minimum value to occur at the internal
reference temperature measuring point, can be reset by
writing any value in this parameter.
CONFIG_
AREA_1...CONFIG_
AREA_15
OOS
The configurable area of FOUNDATION Fieldbus field
diagnostics. One of the four diagnostic events:
• 42 - Corrosion
• 103 - Drift
• 901 - Ambient temperature too low
• 902 - Ambient temperature too high
can be separated from the factory-configured diagnostic
group and categorized individually here. By setting the event
to one of the Field Diagnostic Bits 1-15, the category for this
bit can be configured in the Resource Block to one of the
categories F, C, S, M (→ 93).
STATUS_SELECT_ 42
OOS
The measured value status (BAD, UNCERTAIN, GOOD) can be
configured for the individual diagnostic event
STATUS_SELECT_ 103
OOS
STATUS_SELECT_ 901
OOS
STATUS_SELECT_ 902
OOS
DIAGNOSIS_ SIMULATION_
ENABLE
OOS
Enable/disable simulation of a diagnostic event.
DIAGNOSIS_ SIMULATION_
NUMBER
AUTO - OOS
Use this function to select the diagnostic event to be
simulated.
14.3.9 Transducer Block "Display"
The settings in the "Display" Transducer Block make it possible to display measured values
from the two Transducer Blocks "Sensor 1 + 2" on the optional display. The selection is
made via the DISPLAY_SOURCE_X1 parameter. The number of decimal places displayed
can be configured independently for every channel using the DISP_VALUE_X_FORMAT
parameter. Symbols are available for the units °C, K, F, %, mV, R and Ω. These units are
displayed automatically when the measured value is selected.
The "Display" Transducer Block can show up to 3 values alternately on the display. The
display automatically switches between the values after a configurable time interval
(between 6 and 60 seconds), which can be set in the ALTERNATING_TIME parameter.
Transducer Block “DISPLAY” (device-specific parameters)
Parameter
Write access with
operating mode
(MODE_BLK)
Description
Alternating time
ALTERNATING_TIME
AUTO - OOS
Entry (in s) specifying how long a value should be shown on
the display. Setting from 6 to 60 s.
Display value x
DISP_VALUE_X1)
Read only
Selected measured value:
• Status
• Value