iTEMP TMT85
Diagnostics and troubleshooting
Hauser
43
Category
No.
Status messages
•
ACTUAL_STAT
US_NUMBER
in the
'Advanced
Diagnostics'
Transducer
Block
•
Local display
Error messages in the
relevant Sensor
Transducer Block
Sensor
Transducer Block
measured value
status (default)
Cause of error /
remedy
Output variables
affected
S-
902
Device status
message (FF):
Ambient
temperature too
high
S-902
Local display:
S902 ↔ Measured
value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN
(configurable)
Cause of error:
Reference
temperature <
+85 °C (+185 °F)
Remedy:
Observe ambient
temperature in
accordance with
specification.
SV1, SV2, PV1,
PV2, DT
Transducer_Error = No
error
SUBSTATUS = Non
specific
9.2.4
Category C diagnostics messages
Category
No.
Status messages
•
ACTUAL_STAT
US_NUMBER
in the
'Advanced
Diagnostics'
Transducer
Block
•
Local display
Error messages in the
relevant Sensor
Transducer Block
Sensor
Transducer Block
measured value
status (default)
Cause of error /
remedy
Output variables
affected
C-
402
Device status
message (FF):
Device
initialization
C-402
Local display:
C402 ↔ Measured
value
BLOCK_ERR = Power up QUALITY =
UNCERTAIN
Cause of error:
Device starting/
initializing.
Remedy:
Message is only
displayed during
power-up.
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
Data integrity error
SUBSTATUS = Non
specific
C-
482
Device status
message (FF):
Simulation active
C-482
Local display:
C482 ↔ Measured
value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN
Cause of error:
Simulation is
active.
Remedy:
-
Transducer_Error = No
error
SUBSTATUS =
Substitute
C-
501
Device status
message (FF):
Device reset
C-501
Local display:
C501 ↔ Measured
value
BLOCK_ERR = Other
QUALITY =
UNCERTAIN /
GOOD
Cause of error:
Device reset is
performed.
Remedy:
Message is only
displayed during a
reset.
SV1, SV2, PV1,
PV2, DT
Transducer_Error = No
error
SUBSTATUS = Non
specific / update
event
9.2.5
Corrosion monitoring
Sensor connection cable corrosion can lead to false measured value readings. Therefore
the unit offers the possibility of detecting corrosion before a measured value is affected.
Corrosion monitoring is only possible for RTDs with a 4-wire connection and
thermocouples.
2 different levels can be selected in the CORROSION_DETECTION parameter (see Section
11) depending on the application requirements: