Operation via FOUNDATION Fieldbus
TM
iTEMP TMT85
70
Hauser
Resource Block
Parameter
Index
Parameter
Write access with
operating mode
(MODE_BLK)
Description
61
Maintenance Mask
(FD_MAINT_MASK)
AUTO - OOS
Disables the transmission of device messages to the fieldbus.
69
Maintenance Priority
(FD_MAINT_PRI)
AUTO - OOS
Indicates the alarm priority of the alarm transmitted to the fieldbus.
52
Offspec Active
(FD_OFFSPEC_ACTIVE)
Read only
Indicates whether a diagnostic event of the defined category is currently
pending.
64
Offspec Alarm
(FD_OFFSPEC_ALM)
AUTO - OOS
Alarms that are actively transmitted by the device to the fieldbus.
56
Offspec Map (FD_OFFSPEC_
MAP)
AUTO - OOS
Enable or disable diagnostic events or diagnostic groups for the relevant
category.
60
Offspec Mask (FD_OFFSPEC_
MASK)
AUTO - OOS
Disables the transmission of device messages to the fieldbus.
68
Offspec Priority
(FD_OFFSPEC_PRI)
AUTO - OOS
Indicates the alarm priority of the alarm transmitted to the fieldbus.
72
Recommended Action
(FD_RECOMMEN_ACT)
Read only
Displays the cause of the highest-priority diagnostic event in plain text along
with remedial action.
71
Field Diagnostic Simulate
(FD_SIMULATE)
AUTO - OOS
Makes it possible to simulate the field diagnostic parameters when the
simulation switch is enabled.
50
Field device diagnostic version
(FD_VER)
Read only
The main version of the FF field diagnostic specification which was used for
development purposes for this device.
17
Features (FEATURES)
Read only
Displays the additional functions supported by the device.
Display:
Reports |
Faultstate |
Hard W Lock |
Change Bypass in Auto |
MVC Report Distribution supported Multi-bit Alarm (Bit-Alarm) Support
18
Feature Selection
(FEATURES_SEL)
AUTO - OOS
Use this function to select the additional functions supported by the device.
75
FF communication software
version (FF_COMM_VERSION)
Read only
Displays the version of the FF communication software (stack).
49
Firmware Version
(FIRMWARE_ VERSION)
Read only
Displays the device software version.
25
Free Time (FREE_TIME)
Read only
Displays the free system time available (as a percentage) for the execution of
additional function blocks.
This parameter always displays the value 0 because the function blocks
of the device are preconfigured.
24
Free Space (FREE_SPACE)
Read only
Displays the free space available (as a percentage) for the execution of
additional function blocks.
This parameter always displays the value 0 because the function blocks
of the device are preconfigured.
14
Grant Deny (GRANT_DENY)
AUTO - OOS
Grant or deny a fieldbus host system access authorization to the field device.
15
Hard Types (HARD_TYPES)
Read only
Displays the input signal type for the Analog Input function block.
73
Hardware Version
(HARDWARE_ VERSION)
Read only
Displays the device hardware version.
41
ITK Version (ITK_VER)
Read only
Displays the version number of the supported ITK test.
32
Limit Notify (LIM_NOTIFY)
AUTO - OOS
Use this parameter to specify the number of event reports that can
simultaneously exist as unconfirmed reports.
Options:
0 to 4
Factory setting:
4