iTEMP TMT85
Operation via FOUNDATION Fieldbus
TM
Hauser
85
In addition, the entire status information of the device and the maximum/minimum
indicators for the two sensor values and the internal temperature are also available.
Transducer Block “ADVANCED DIAGNOSTIC” (device-specific parameters)
Parameter
Write access
with operating
mode
(MODE_BLK)
Description
Corrosion detection
(CORROSION_ DETECTION)
OOS
• OFF: Corrosion detection off
• ON: Corrosion detection on
Only possible for RTD 4-wire connection and
thermocouples (TC).
Sensor Drift monitoring
(SENSOR_
DRIFT_MONITORING)
OOS
Drift between SV1 and SV2 is displayed according to the field
diagnostic configuration of diagnostic event "103 - Drift":
• OFF: Sensor drift monitoring off (diagnostic event 103 has
been deactivated)
• ON: Sensor drift monitoring on (when a drift occurs,
diagnostic event 103 is displayed with the category
configured for the event)
Sensor Drift mode (SENSOR_
DRIFT_MO DE)
OOS
Select whether a status is generated if the value set in the
SENSOR_DRIFT_LIMIT parameter is undershot
(Undershooting) or overshot (Overshooting).
If "Overshooting" is selected, the corresponding
diagnostic event is generated if the limit value is
overshot (SENSOR_DRIFT_LIMIT). In the case of
"Undershooting", the diagnostic event is output if the
limit value is undershot.
Sensor Drift alert value
(SENSOR_
DRIFT_ALERT_VALUE)
OOS
Limit value of the permitted drift from 1 to 999.99.
System Alarm delay
(SYSTEM_ ALARM_DELAY)
OOS
Alarm hysteresis: Value specifying the time a diagnostic
event (F, C, S, M) and measured value status (Bad or
Uncertain) is delayed until the status is output. Can be set
between 0 and 10 seconds.
This setting does not affect the display.
Actual Status Category /
Previous Status Category
(ACTUAL_ STATUS_ CATE
GORY / PREVIOUS_
STATUS_ CATEGORY)
Read only /
AUTO - OOS
Current/last status category
• Good: No errors detected
• F: Failure: Error detected
• C: Function check: Device is in the service mode
• S: Out of Spec.: Device is being operated outside the
specifications
• M: Maintenance required
• Not categorized: No Namur category has been selected for
the current diagnostic event.