Commissioning
iTEMP TMT85
34
Hauser
A0042921
15
Screen displayed in the "NI-FBUS Configurator" configuration program (National Instruments) once the
connection is established
Device designation in the Configurator (EH_TMT85_xxxxxxxxxxx = tag name
PD_TAG) and block structure
Configuring the “Resource Block” (base index 400)
6. Open the Resource Block.
7. When the device is delivered, the hardware write protection is disabled so the write
parameters can be accessed via the FF. Check this state via the WRITE_LOCK
parameter: – write protection is enabled = LOCKED – write protection is disabled =
NOT LOCKED Disable write protection if necessary, → 26.
8. Enter the desired name for the block (optional). Factory setting: RS_xxxxxxxxxxx
9. Set the operating mode in the MODE_BLK parameter group (TARGET parameter) to
AUTO.
Configuring the "Transducer Blocks"
The individual Transducer Blocks comprise various parameter groups arranged by device-
specific functions:
Temperature sensor 1
→ Transducer Block “TB_S1_xxxxxxxxxxx” (base index: 500)
Temperature sensor 2
→ Transducer Block “TB_S2_xxxxxxxxxxx” (base index: 600)
Local display functions
→ Transducer Block “TB_DISP_xxxxxxxxxxx” (base index: 700)
Advanced diagnostics
→ Transducer Block “TB_ADVDIAG_xxxxxxxxxx” (base index: 800)
10. Enter the desired name for the block (optional). For factory settings, see the table
above. Set the operating mode in the MODE_BLK parameter group (TARGET
parameter) to AUTO.
Configuring the "Analog Input function blocks"
The device has 2 x three Analog Input function blocks which can be assigned to the
different process variables as desired. The following section describes an example for the
Analog Input function block 1 (base index 900).
11. Enter the required name for the Analog Input function block (optional). Factory
setting: AI_1_xxxxxxxxxxx