iTEMP TMT85
Commissioning
Hauser
33
8.3.1
Initial commissioning
The following description takes you step-by-step through the device commissioning
process and all the necessary configurations for the FOUNDATION Fieldbus
TM
:
1. Open the configuration program.
2. Load the device description files or the CFF file into the host system or the
configuration program. Make sure you are using the right system files (see Section
5.4).
3. Make a note of the DEVICE_ID on the device nameplate to identify the device in the
4. Switch on the measuring device → 31.
The first time you establish a connection, the device responds as follows in the
configuration program:
• EH_TMT85_xxxxxxxxxxx (tag name PD-TAG)
• 452B4810CE-xxxxxxxxxxx (DEVICE_ID)
• Block structure:
Display text (xxx... = serial number)
Base index
Description
RS_xxxxxxxxxxx
400
Resource Block
TB_S1_xxxxxxxxxxx
500
Transducer Block temperature sensor 1
TB_S2_xxxxxxxxxxx
600
Transducer Block temperature sensor 2
TB_DISP_xxxxxxxxxxx
700
Transducer Block “Display” (local display)
TB_ADVDIAG_xxxxxxxxxxx
800
Transducer Block “Advanced Diagnostic”
AI_1_xxxxxxxxxxx
900
Analog Input function block 1
AI_2_xxxxxxxxxxx
1000
Analog Input function block 2
AI_3_xxxxxxxxxxx
1100
Analog Input function block 3
PID_xxxxxxxxxxx
1200
PID function block
ISEL_xxxxxxxxxxx
1300
Input Selector function block
The device is delivered from the factory with the bus address "247" and is therefore in
the 232 to 247 address range which is reserved for changing the address of field
devices. A lower bus address should be assigned to the device for commissioning.
5. Using the DEVICE_ID noted, identify the field device and assign the desired tag name
(PD_TAG) to the fieldbus device in question. Factory setting:
EH_TMT85_xxxxxxxxxxx (xxx... = serial number).