Diagnostics and troubleshooting
iTEMP TMT85
40
Hauser
9.2.1
Category F diagnostics messages
Category
No.
Status messages
•
ACTUAL_STAT
US_NUMBER
in the
'Advanced
Diagnostics'
Transducer
Block
•
Local display
Error messages in the
relevant Sensor
Transducer Block
Sensor
Transducer Block
measured value
status (default)
Cause of error /
remedy
Output variables
affected
F-
041
Device status
message (FF):
Sensor line break
F-041
Local display:
F041
BLOCK_ERR = Other |
Input Failure
QUALITY = BAD
Cause of error:
1. Electr.
interruption of
sensor or sensor
wiring.
2. Incorrect setting
for type of
connection in the
SENSOR_
CONNECTION
parameter.
Remedy:
Re 1.) Reestablish
electr. connection
or replace sensor.
Re 2.) Configure
correct type of
connection.
SV1, SV2, also
PV1, PV2
depending on the
configuration
Transducer_Error =
Mechanical failure
SUBSTATUS =
Sensor failure
F-
043
Device status
message (FF):
Sensor short
circuit
F-043
Local display:
F043
BLOCK_ERR = Other
Input failure
QUALITY = BAD
Cause of error:
Short circuit
detected at the
sensor terminals.
Remedy:
Check the sensor
and sensor wiring.
SV1, SV2, also
PV1, PV2
depending on the
configuration
Transducer_Error =
Mechanical failure
SUBSTATUS =
Sensor failure
F-
221
Device status
message (FF):
Reference
measurement
F-221
Local display:
F221
BLOCK_ERR = Other
QUALITY = BAD
Cause of error:
Internal reference
junction defective.
Remedy:
Device defective,
replace
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
General error
SUBSTATUS =
Device failure
F-
261
Device status
message (FF):
Electronic failure
F-261
Local display:
F261
BLOCK_ERR = Other
QUALITY = BAD
Cause of error:
Electronics error.
Remedy:
Device defective,
replace
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
Electronic failure
SUBSTATUS =
Device failure
F-
283
Device status
message (FF):
Memory error
F-283
Local display:
F283
BLOCK_ERR = Other
QUALITY = BAD
Cause of error:
Error in memory.
Remedy:
Device defective,
replace
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
Data integrity error
SUBSTATUS =
Device failure
F-
431
Device status
message (FF):
No calibration
F-431
Local display:
F431
BLOCK_ERR = Other
QUALITY = BAD
Cause of error:
Error in calibration
parameters.
Remedy:
Device defective,
replace
SV1, SV2, PV1,
PV2, DT
Transducer_Error =
Calibration error
SUBSTATUS =
Device failure