background image

Dok Nr

. 2.204.002.4 - V

ers. 1.2

Art. Nr

. 33.03.154

www

.janitza.com

Janitza electronics GmbH
Vor dem Polstück 1
D-35633 Lahnau
Support Tel. 0049 6441 9642-22
Fax 0049 6441 9642-30
E-mail: [email protected]
Internet: http://www.janitza.com

FBM series  
I/O modules

Functional description

UMG604 - UMG605 - UMG508 - UMG511

Item no.:   15.06.075 / 15.06.076 / 15.06.077
 

15.06.078 / 15.06.079

Содержание 15.06.075

Страница 1: ...cs GmbH Vor dem Polstück 1 D 35633 Lahnau Support Tel 0049 6441 9642 22 Fax 0049 6441 9642 30 E mail info janitza com Internet http www janitza com FBM series I O modules Functional description UMG604 UMG605 UMG508 UMG511 Item no 15 06 075 15 06 076 15 06 077 15 06 078 15 06 079 ...

Страница 2: ...tion diagram FBM10I 12 Connection diagram FBM10PT1000 PT100 13 Connection diagram FBM DI8AI8 13 LED display 14 Register assignment FBM10R 14 Register assignment FBM10l 15 Register assignment FBM10PT1000 PT100 15 Register assignment FBM DI8AI8 16 Example control of the FBM10R module with JASIC 18 Temperature measurement APP for module FBM10PT1000 20 JASIC programs for module DI8AI8 22 Control with ...

Страница 3: ...ectronics GmbH Vor dem Polstück 1 D 35633 Lahnau Germany Trademarks All trademarks and their resulting rights belong to the respective holders of these rights Disclaimer Janitza electronics GmbH takes no responsibility for errors or defects within this operating manual and takes no responsibility for keeping the contents of this operating manual up to date Comments on the operating manual We welco...

Страница 4: ...tem and device from power supply before beginning work m Attention Please follow the documentation This symbol warns of possible dangers that can arise during installation commissioning and use C Note Meaning of the symbols The following pictograms are used in the operating manual at hand ...

Страница 5: ...suse and or negligence in terms of the war ranty for the product and therefore eliminates the warranty for covering any potential damages resulting from this This device is to be operated and maintained exclusively by specialized personnel Specialized personnel are persons that based on their respective training and experience are qualified to recognize risks and prevent potential dangers that can...

Страница 6: ...076 has 10 digital inputs The fieldbus module FBM P10PT1000 item no 15 06 077 has 10 temperature inputs The module FBM DI8 AI8 item no 15 06 079 has 8 digital and 8 analog inputs The I O modules of the FBM series are con nected to the RS485 interface of the power analyzer The analyzer works in Modbus Mas ter Mode in doing so The maximum stitch length cable length between the master and the module ...

Страница 7: ...ress on a UMG604 UMG605 1 Simultaneously press key 1 and key 2 one second 2 You are now in the parameter menu The letters PRG identify this menu C Note Key 1 Change segment selection Key 2 Change value long short The following parameters must be parameterized for the Emax function on the device Parameter Designation Parameter recommendation Settings 205 TCP mode 0 Fixed IP 203 RS485 mode 1 Master ...

Страница 8: ...e ESC key in order to access the configuration menu 2 Go into the communication menu 3 Set the parameters from the following list recommendation Proposal DHCP Off Address 192 168 1 10 Net mask 255 255 255 0 Gateway Protocol Modbus Gateway Address 33 Baud rate 38400 ...

Страница 9: ...mpany network can vary The IP settings are shown here with the Windows XP operating system as an example It should be noted here that for a point to point connection the first three segments of the IP should be the same The Subnet mask should be exactly the same for the PC and the measurement device Give your computer the IP 192 168 1 1 recommendation and the subnet mask 255 255 255 0 Confirm with...

Страница 10: ... cable must be shielded and drilled Example connection UMG604 605 UMG604 terminal 23 A FBM 10R FBM 10I FBM 10PT1000 FBM DI8 AI8 on terminal A UMG604 terminal 22 B FBM 10R FBM 10I FBM 10PT1000 FBM DI8 AI8 on terminal B Correct Incorrect DIP switch For serial communication several default settings must be implemented These settings are car ried out on the fieldbus device using the ten available DIP ...

Страница 11: ...OFF ON OFF ON 41 OFF ON OFF ON OFF ON 42 ON ON ON ON ON ON 63 Setting occurs as with a binary number Parity The parity must be established with serial communica tion The following assignments are possible with the fieldbus device DIP 7 8 Parity OFF OFF NONE ON OFF ODD ON ON EVEN Baud rate DIP switches 9 and 10 The speed for the data transmission baud rate must also be established There are four di...

Страница 12: ...sausgänge Relay Output DIP Schalter RS 485 c Connection of the device may only occur in de energized state and if it must be connected under voltage the GND must first be connected m Bus polarization necessary Connection diagram FBM10I Digital inputs 24 V DC 5mA inputs Versorgungs spannung Auxiliary Supply Digitaleingänge Digital Inputs Digitaleingänge Digital Inputs DIP Schalter RS 485 ...

Страница 13: ...ed to connect the 0 voltage line C for accuracy reasons Connection terminals for the potential free contacts are implemented separately C Note The 10V analog outputs are in preparation and are not yet integrated in the current version FBM10PT1000 100 c Connection of the device may only occur in de energized state and if it must be connected under voltage the GND must first be connected m Bus polar...

Страница 14: ...on terminal Type I O module Type Modbus RTU R1 Relay output 1 Coil 0 R2 Relay output 2 Coil 1 R3 Relay output 3 Coil 2 R4 Relay output 4 Coil 3 R5 Relay output 5 Coil 4 R6 Relay output 6 Coil 5 R7 Relay output 7 Coil 6 R8 Relay output 8 Coil 7 R9 Relay output 9 Coil 8 R10 Relay output 10 Coil 9 Register assignment FBM10R Word addressing R1 R10 Holding register 0 Info Hardware version Input registe...

Страница 15: ...Digital input 5 Input status 4 DI6 Digital input 6 Input status 5 DI7 Digital input 7 Input status 6 DI8 Digital input 8 Input status 7 DI9 Digital input 9 Input status 8 DI10 Digital input 10 Input status 9 Register assignment FBM10l Word addressing DI1 DI10 Input register 0 Info Hardware version Input register 1000 Info Software version Input register 1001 Note MOD Input status fc 2 MOD Input re...

Страница 16: ...ister T4 T5 Analog input 5 Input register T5 T6 Analog input 6 Input register T6 T7 Analog input 7 Input register T7 T8 Analog input 8 Input register T8 T9 Analog input 9 Input register T9 Register assignment FBM10PT1000 PT100 C Note The 10V analog outputs are in preparation and are not yet integrated in the current version Info Hardware version Input register 1000 Info Software version Input regi...

Страница 17: ...1 4 20mA Analog input 1 Input register 1 AI2 4 20mA Analog input 2 Input register 2 AI3 4 20mA Analog input 3 Input register 3 AI4 4 20mA Analog input 4 Input register 4 AI5 4 20mA Analog input 5 Input register 5 AI6 4 20mA Analog input 6 Input register 6 AI7 4 20mA Analog input 7 Input register 7 AI8 4 20mA Analog input 8 Input register 8 Register assignment FBM DI8AI8 Word addressing DI1 DI8 Inp...

Страница 18: ...ite access to the modules C Information on the graphic programming can be found in the functional description Graphic programming from Janitzaelectronics GmbH C Attention For the function Write Read Modbus is at least the license of GridVis Enterprise Art Nr 51 00 170 required Example The digital outputs of the FBM10R are controlled using a write Modbus function mo dule ...

Страница 19: ...FBM Serie 19 Example The digital inputs of the FBM10l are read out using a read Modbus function module ...

Страница 20: ...FBM Serie 20 Temperature measurement APP for module FBM10PT1000 ...

Страница 21: ...FBM Serie 21 After APP installation the values can also be saved The programming occurs graphically ...

Страница 22: ... the analogue measurement values in the UMG Installation to a free program location The JASIC program is installed via the button Load from file Once the program has be transfer red a debug output takes place in the Debug Log tab The device address for the FBM module is cited directly in the source text Default device address 1 Important The UMG604 must possess a dif ferent device address and must...

Страница 23: ...4 26006 FLOAT 4 Byte FBM module analog input 5 26008 FLOAT 4 Byte FBM module analog input 6 26010 FLOAT 4 Byte FBM module analog input 7 26012 FLOAT 4 Byte FBM module analog input 8 26014 FLOAT 4 Byte FBM module digital input 1 26020 SHORT 2 Byte FBM module digital input 2 26021 SHORT 2 Byte FBM module digital input 3 26022 SHORT 2 Byte FBM module digital input 4 26023 SHORT 2 Byte FBM module digi...

Страница 24: ...FBM Serie 24 Control with modbus diagnostics tool for module DI8AI8 Download at http download janitza de download_direkt Tools Modbus Diagnose zip ...

Страница 25: ...FBM Serie 25 RS485 communication error ...

Страница 26: ...measurement values from module FBM DI8AI8 Install the program JASIC FBM DI8AI8 Aufzeichnung jas to a free JASIC program location It is subsequently possible to change the names in the recording dialogue box It is also possible to set a scale ...

Страница 27: ...FBM Serie 27 ...

Страница 28: ...10 000 4 20mA resolution 4 000 20 000 Environmental temperature 10 C 50 C Storage temperature 20 C 70 C Accuracy 0 1 for temperature measurement PT1000 Temperature coefficient 0 003 K for temperature measurement PT1000 Terminal Screw terminal plug terminal 0 14 to 1mm pursuant to VDE Housing 45mm series production system Dimensions H x W x D 90 x 88 x 58 mm Installation Mounting rail TS35 or direc...

Отзывы: