FBM-Serie
22
JASIC programs for module DI8AI8
JASIC-FBM-DI8AI8-globale-Variablen.jas
JASIC-FBM-DI8AI8-Aufzeichnung.jas
These Jasic programs read out the FBM modules and place the values in global variables.
The program „JASIC-FBM-DI8AI8-Aufzeichnung.jas“ stores the analogue measurement values in
the UMG.
Installation to a free program location:
The JASIC program is installed via the button „Load from file“. Once the program has be transfer-
red, a debug output takes place in the „Debug Log“ tab.
The device address for the FBM module is
cited directly in the source text.
Default device address: 1
Important:
The UMG604 must possess a dif-
ferent device address and must be located on
the modbus master. The Baud rate is 38000
Baud.