Cerabar M, Deltapilot M
Commissioning
Hauser
49
8.3
Commissioning without an operating menu
8.3.1
Pressure measuring mode
The following functions are possible via the keys on the electronic insert:
• Position adjustment (zero point correction)
• Setting the lower range value and upper range value
• Operation must be unlocked → 41
• The device is configured for the "Pressure" measuring mode as standard. You can
change the measuring mode via the "Measuring mode" parameter → 51.
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
L
WARNING
Changing the measuring mode affects the span (URV)!
This can result in product overflow.
‣
If the measuring mode is changed, the span setting (URV) must be verified and, if nec-
essary, reconfigured!
Perform position adjustment (see the information at the start of the "Commissioning" section)
1
Pressure is present at the device.
2
Press the "Zero" and "Span" keys simultaneously for at least 3 s.
3
Does the LED on the electronic insert light up briefly?
4
Yes
No
5 Applied pressure for position adjustment has been
accepted.
Applied pressure for position adjustment has not been
accepted. Observe the input limits.
Setting the lower range value
1
The desired pressure for the lower range value is present at the device.
2
Press the "Zero" key for at least 3 s.
3
Does the LED on the electronic insert light up briefly?
4
Yes
No
5
Applied pressure for lower range value has been
accepted.
Applied pressure for lower range value has not been
accepted. Observe the input limits.
Setting the upper range value
1
The desired pressure for the upper range value is present at the device.
2
Press the "Span" key for at least 3 s.
3
Does the LED on the electronic insert light up briefly?
4
Yes
No
5
Applied pressure for upper range value has been
accepted.
Applied pressure for upper range value has not been
accepted. Observe the input limits.