Cerabar M, Deltapilot M
Diagnostics and troubleshooting
Hauser
61
10
Diagnostics and troubleshooting
10.1 Diagnostic events
10.1.1 Diagnostic message
Faults detected by the self-monitoring system of the measuring device are displayed as a
diagnostic message in alternation with the measured value display.
Status signals
The messages that can occur are listed in the table. The ALARM STATUS parameter shows
the message with the highest priority. The device has four different status information
codes according to NE107:
A0013956
"Failure"
A device error has occurred. The measured value is no longer valid.
A0013957
"Maintenance required"
Maintenance is required. The measured value remains valid.
A0013959
"Function check"
The device is in service mode (e.g. during a simulation).
A0013958
"Out of specification"
The device is being operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
• Outside of the configuration performed by the user (e.g. level outside configured span)
Diagnostic event and event text
The fault can be identified by means of the diagnostic event.
The event text helps you by providing information about the fault.
Diagnostic event
Status signal
Event number
Event text
↓
↓
↓
Example
A0013958
841
Sensor range
3-digit number
If two or more diagnostic events are queued simultaneously, only the diagnostic message
with the highest priority is displayed.
Other diagnostic messages that are queued can be viewed in the
Diagnostic list
submenu.
Past diagnostic messages that are no longer queued are shown in the
Event logbook
submenu.