Installation
Hauser
23
4.4.4
Wall and pipe mounting (optional)
Hauser offers a mounting bracket for installation on pipes or walls (for pipe
diameters from 1 ¼" to 2").
86 (3.39)
122 (4.8)
140 (5.5)
70 (2.76)
52 (2.05)
ø6 (0.24)
ø42...60 (1.65...2.36)
A0024812
Engineering unit mm (in)
Please note the following when mounting:
• Devices with capillary tubes: mount capillaries with a bending radius ≥
100 mm (3.94 in).
• When mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at
least 5 Nm (3.69 lbf ft).