Commissioning
Cerabar M, Deltapilot M
58
Hauser
Description
1
Select the "Pressure" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
‣
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
p
[mbar]
20
B
4
A
0
300
I
[mA]
A0031032
A
See table, step 3.
B
See table, step 4.
2
Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3
Select the "Set LRV" parameter.
Menu path: Setup → Set LRV
Enter the value for the "Set LRV" parameter (here 0 mbar) and confirm. This pressure
value is assigned to the lower current value (4 mA).
4
Select the "Set URV" parameter.
Menu path: Setup → Set URV
Enter the value for the "Set URV" parameter (here 300 mbar (4.5 psi)) and confirm. This
pressure value is assigned to the upper current value (20 mA).
5
Result:
The measuring range is configured for 0 to +300 mbar (0 to 4.5 psi).