Installation
Cerabar M, Deltapilot M
26
Hauser
4.5
Installing the Deltapilot M
• Due to the orientation of the Deltapilot M, there may be a shift in the zero point, i.e.
when the container is empty or partially full, the measured value does not display zero.
You can correct this zero point shift → 36 "Function of the operating elements".
• The local display can be rotated in 90° stages.
• Hauser offers a mounting bracket for installing on pipes or walls. → 23, Sec-
tion "Wall and pipe mounting (optional)".
4.5.1
General installation instructions
NOTICE
Damage to the device!
If a heated device is cooled during a cleaning process (e.g. by cold water), a vacuum devel-
ops for a short time and, as a result, moisture can enter the sensor via the pressure com-
pensation (1).
‣
In this case, mount the device so that the pressure compensation (1) point downwards.
1
1
1
1
A0028471
• Keep the pressure compensation and GORE-TEX® filter (1) free from contamination.
• Do not clean or touch process membranes with hard or pointed objects.
• The process membrane in the rod and cable version is protected against mechanical
damage by a plastic cap.
• The device must be installed as follows in order to comply with the cleanability require-
ments of the ASME-BPE (Part SD Cleanability):
A0028472