Cerabar M, Deltapilot M
System integration
Hauser
43
7
System integration
7.1
Process data
The measuring device has a current output.
• In the IO-Link communication mode, pin 4 of the M12 plug is reserved exclusively for
communication
• The current output at pin 2 of the M12 plug is always active and can be optionally deac-
tivated via IO-Link
• The measuring device's process data are transmitted cyclically as per SSP 4.3.3
Sub-
index
Bit-off-
set
Data type
Permitted values
Name
Offset / gradient
Description
1
80
Float32
-
Pressure
mbar: 0 / 0.01
bar: 0 / 0.00001
mmH2O: 0 / 0.101973
mH2O: 0 / 0.000101973
ftH2O: 0 / 0.00033456
inH2O: 0 / 0.00401477
Pa: 0 / 1
kPa: 0 / 0.001
MPa: 0 / 0.000001
psi: 0 / 0.0001450326
mmHg: 0 / 0.0075006
inHg: 0 / 0.0002953
kgf / cm
2
: 0 / 0.0000101973
Current pressure
2
48
Float32
-
Level
-
Current level
3
16
Float32
-
Temperature
C: 0 / 0.01
F: +32 / 0.018
K: +273.15 / 0.01
Actual temperature
4
8
8-bit UInteger • 36 = Error
• 60 = Function check
• 120 = Outside specifications
• 128 = Good
• 129 = Simulation
• 164 = Maintenance required
Summary status -
Summary status as per PI
specification
5
6
2-bit UInteger • 0 = Default setting
• 1 = Calibrated
Level status
-
Current level status
6
0
6-bit UInteger • 0 = SSCx OFF
• 1 = SSCx_ON
Switching of the
signal channel
-
Binary process data content
that signals a certain status
of the evaluation signal.
7.2
Reading out and writing device data (ISDU – Indexed
Service Data Unit)
Device data are always exchanged acyclically and at the request of the IO-Link master.
Using the device data, the following parameter values or device statuses can be read out: