Description of device parameters
Cerabar M, Deltapilot M
82
Hauser
Write permission
Operators/Service engineers/Expert
Description
Set the upper-range value – reference pressure is present at the device.
The pressure for the upper current value (20 mA) is present at the device. Use the "Con-
firm" option to assign the applied pressure value to the upper current value.
Prerequisite:
Pressure measuring mode
Options
• Cancel
• Confirm
Factory setting
Cancel
Set LRV (013, 168)
Write access
Operator/Service engineer/Expert
Description
Set the pressure value, level or content for the lower current value (4 mA).
Factory setting
• 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
• 0.0 m
3
/h in Flow measuring mode
Get URV (pressure measuring mode) (016)
Write permission
Operators/Service engineers/Expert
Description
Set the upper-range value – reference pressure is present at the device.
The pressure for the upper current value (20 mA) is present at the device. Use the "Con-
firm" option to assign the applied pressure value to the upper current value.
Prerequisite:
Pressure measuring mode
Options
• Cancel
• Confirm
Factory setting
Cancel
Set URV (014, 169)
Write permission
Operator/Maintenance/Expert
Description
Set the pressure value, level or content for the upper current value (20 mA).