Cerabar M, Deltapilot M
Commissioning
Hauser
53
Pos. zero adjust (007) (gauge pressure sensors)
Write permission
Operator/Maintenance/Expert
Description
Pos. zero adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.
Example
• Measured value = 2.2 mbar (0.033 psi)
• You correct the measured value via the "Pos. zero adjust" parameter with the "Confirm"
option. This means that you are assigning the value 0.0 to the pressure present.
• Measured value (after pos. zero adjustment) = 0.0 mbar
• The current value is also corrected.
Selection
• Confirm
• Cancel
Factory setting
Cancel
8.5
Configuring level measurement
8.5.1
Information on level measurement
• The limit values are not checked, i.e. the values entered must suit the sensor and
measuring task for the device to be able to measure correctly.
• Customer-specific units are not possible.
• There is no unit conversion.
• The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure" and
"Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a mes-
sage displayed, if the values are too close together.
8.5.2
Overview of level measurement
Measuring task
Level selec-
tion
Measured variable options
Description
Measured value display
Calibration is performed by
entering two pressure-level
value pairs.
"In pressure"
Via the "Output unit" parame-
ter:
%, level, volume or mass
units.
• Calibration with reference pressure (wet
• Calibration without reference pressure (dry
The measured value dis-
play shows the measured
value.
8.5.3
"In pressure" level selection: Calibration with reference
pressure (wet calibration)
Example:
In this example, the level in a tank should be measured in "m". The maximum level is
3 m (9.8 ft).
The pressure range is derived from the level and the density of the medium. In this case,
the device sets the pressure range to 0 to 300 mbar (0 to 4.5 psi).