Cerabar M, Deltapilot M
Description of device parameters
Hauser
75
Write permission
Maintenance/Expert
Description
Position adjustment – the pressure difference between the set point and the measured
pressure must be known.
Example
• Measured value = 982.2 mbar (14.73 psi)
• You correct the measured value with the value entered, e.g. 2.2 mbar (0.033 psi) via the
"Calib. offset" parameter. This means that you are assigning the value to the pressure
present 980.0 mbar (14.7 psi).
• Measured value (after pos. zero adjustment) = 980.0 mbar (14.7 psi)
• The current value is also corrected.
Factory setting
0.0
Damping value (017)
Write permission
Operators/Service engineers/Expert
(if the "Damping" DIP switch is set to "on")
Description
Enter the damping time (time constant τ).
The damping affects the speed at which the measured value reacts to changes in pressure.
Input range
0,0...999,0 s
Factory setting
2.0 or as per order specifications
Press. eng. unit (125)
Write permission
Operator/Maintenance/Expert
Description
Select the pressure unit. If a new pressure unit is selected, all pressure-specific parameters
are converted and displayed with the new unit.
Selection
• mbar, bar
• mmH2O, mH2O
• inH2O, ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
2
Factory setting
mbar or bar depending on the nominal measuring range of the sensor, or as per order
specifications.
Temp. eng. unit (126)