Electrical connection
Cerabar M, Deltapilot M
32
Hauser
5.3
Terminals
• Supply voltage: 0.5 to 2.5 mm
2
(20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm
2
(20 to 12 AWG)
5.4
Cable specification
5.4.1
IO-Link
Hauser recommends using twisted, four-core cable.
5.5
Load for current output
In order to guarantee sufficient terminal voltage, a maximum load resistance R
L
(including
line resistance) must not be exceeded depending on the supply voltage U
B
of the supply
unit.
[ ]
W
20
30
11,5
0
1022
587
217
U
[V]
1
2
R
R
L
L
max
max
£
-
U
6.5V
23mA
B
B
A0045615
1
Power supply 11.5 to 30 V
DC
2
R
Lmax
maximum load resistance
U
B
Supply voltage
• Output of failure current and display of "M803" (Output: MIN alarm current)
• Periodic checking to establish if it is possible to quit fault state
5.6
Field Xpert SMT70, SMT77
The Field Xpert SMT70 tablet PC for device configuration enables mobile plant asset man-
agement in hazardous (Ex Zone 2) and non-hazardous areas. It is suitable for commission-
ing and maintenance staff. It manages Hauser and third-party field instruments
with a digital communication interface and documents the progress of the work. The
SMT70 is designed as a complete solution. It comes with a pre-installed driver library and
is an easy-to-use, touch-enabled tool for managing field devices throughout their entire
life cycle.
The Field Xpert SMT77 for device configuration enables mobile plant asset management
in areas categorized as Ex Zone 1. It is suitable for commissioning and maintenance staff
for easy management of field instruments with a digital communication interface. The
touch-enabled tablet PC is designed as a complete solution. It comes with comprehensive
pre-installed driver libraries and offers users a modern software user interface to manage
field instruments throughout the entire life cycle.
Required tool: "IO-Link IODD Interpreter DTM"