Installation
Cerabar M, Deltapilot M
24
Hauser
4.4.5
Assembling and mounting the "separate housing" version
r
³
120 (4.72)
2
3
4
5
6
1
7
7
A0028494
1
In the case of the "separate housing" version, the sensor is delivered with the process connection and cable
ready mounted.
2
Cable with connection jack
3
Pressure compensation
4
Connector
5
Locking screw
6
Housing mounted with housing adapter, included
7
Mounting bracket provided, suitable for pipe and wall mounting (for pipe diameters from 1 ¼" up to 2")
Engineering unit mm (in)
Assembly and mounting
1. Insert the connector (item 4) into the corresponding connection jack of the cable
(item 2).
2. Plug the cable into the housing adapter (item 6).
3. Tighten the locking screw (item 5).
4. Mount the housing on a wall or pipe using the mounting bracket (item 7). When
mounting on a pipe, tighten the nuts on the bracket uniformly with a torque of at
least 5 Nm (3.69 lbf ft). Mount the cable with a bending radius (r) ≥
120 mm (4.72 in).
Routing the cable (e.g. through a pipe)
You require the cable shortening kit.
Order number: 71125862
For details on mounting, see SD00553P/00/A6.