13 Technical Data VS 3015 C / SIOX
13.1 Electrical Data VS 3015 C / SIOX
VS 3015 C
SIOX extension module
Operating voltage
230 V AC, 200 ... 265 V AC, 50/60 Hz
24 V DC / 9 V DC
supply via VS 3015 C
Rated power
24 VA
3.1 W
Leakage current over PE
(protective earth)
max 1 mA
Rated
surge voltage
2.5 kV for overvoltage category II
4.0 kV for overvoltage category III
Digital inputs
24 x 230 V AC, floating output
12 x 230 V AC, floating output
Relay outputs
6 x normally open contact, 250 V AC, floating
output, min 10 mA
Load type: ohmic: max. 6 A, inductive: max. 3 A,
cos phi = 0.4
4 x changeover contact, 250 V AC, floating
output, min 10 mA
Load type: ohmic: max. 6 A, inductive: max. 3 A,
cos phi = 0.4
4 x normally open contact, 250 V AC, floating
output, min 10 mA
Load type: ohmic: max. 6 A, inductive: max.
3 A, cos phi = 0.4
4 x changeover contact, 250 V AC, floating
output, min 10 mA
Load type: ohmic: max. 6 A, inductive: max.
3 A, cos phi = 0.4
Manual control switch
The pack controller as well as the SIOX extension modules have manual control switches so
that the regulation can be manually overridden in emergency operation, see chapter
Manual / automatic emergency mode selection
.
Analogue inputs
1)
13 x Pt1000 2-wire temperature sensor
2 x Pt1000 4-wire temperature sensor
3 x pressure transmitter 4..20 mA / 0..10 V
1 x humidity sensor 4..20 mA / 0..10 V
(all inputs can be adjusted internally using
jumpers)
-
Analogue outputs
1)
4 x 0..10 V / 4..20 mA,
can be adjusted internally using jumpers
0..10 V (load min. 1 kΩ) / 4..20 mA (resistance
max. 800 ohm)
-
Warning about dangerous electrical voltage! Danger to life - Danger of electric shock!
Overvoltage category III (test voltage 4.0 kV) / contamination degree 2:
All connections of the
device provided for operation with 230 V AC supply voltage
must
be wired with the same phase
conductor. 400 V AC between neighbouring connection terminals is
not
permitted!
Overvoltage category II (test voltage 2.5 kV) / contamination degree 2
or
overvoltage category II (test voltage 2.5 kV) / contamination degree 1:
Different phase conductors
may be used. 400 V AC between neighbouring connection terminals is permitted!