14.01.2019
150/185
Vari.Z.AUS POS: XXXXX
Input Default
Dim.
...
Vari.Z.AUS S12 XXX s
3..250 120
sec.
VS 3015 C base module: 1 - max. 4 capacity stages
with first SIOX extension module 1 - max. 8 capacity stages
with second SIOX extension module 1 - max. 12 capacity stages
•
Menu 3-2-1-4 LP Control Night
ND-REG N. POS:
XXXXX
Input Defa
ult
Dim
.
to-Max. XXX °C
Max. t0 setpoint for setpoint shift
-50..1
0
-6
°C
tr-min. XXX °C
Minimum room temperature for setpoint shift (only visible if t0-shift via room
temperature is active - screen 3-2-1-2-a)
-25..2
0
15
°C
to-Min. XXX °C
Minimum t0 setpoint for setpoint shift
-50..1
0
-10
°C
tr-Max. XXX °C
Maximum room temperature for setpoint shift (only visible if t0-shift via room
temperature is active - screen 3-2-1-2-a)
-18..3
5
25
°C
Feuchteschieb. X
Humidity shift activated YES/NO
Y/N
N
-
Basisz.LeiStu. ON
→
Display basic times t
b
ON
→
Screen
3-2-1-4-a
Screen
3-2-1-4-b
Screen
3-2-1-4-c
Screen
3-2-1-4-d
Vari.Z.LeiStu. ON
→
Display of the variable times t
v
ON
→
Basisz.LeiStu. OFF
→
Display basic times t
b
OFF
→
Vari.Z.LeiStu. OFF
→
Display of the variable times t
v
OFF
→
Neutrale Zone XX K Switching hysteresis for step control
1..10
4
K
NZ Drehz.reg. 0K
Neutral zone for the loading and unloading of fixed-speed compressors during
combined control
0..6
0
K
Regelkonstante XX
K
Max. control error for variable control times
1..15
10
K
Reg.m.Verd.AUS
Deactivate high pressure controller when the last compressor is switched off Y/N
Y/N
N
-
•
Screen 3-2-1-4-a Basic time capacity stage ON