14.01.2019
141/185
AUSBAU
POS: XXXXX
Input Def
ault
Di
m.
Öl/HD-
Störung X
Oil pressure difference switch / HP switch compressor YES/NO
Y/N N
-
Text Öl/HD-
Stör →
Selection of the message text that will be output in the case of oil pressure or high pressure
compressor fault
→
Screen
3-1-c
Verz.Öl/HD-
St. xx m
Delay time for the messages from menu 3-1-c
0..10 0
Mi
n.
Freig.Leist.
Stufen →
Display of the capacity stages
→
Screen
3-1-d
Notbetrieb
X
Emergency operation YES/NO
Y/N N
-
Anz.Stuf.No
tb. X
Number of capacity stages for emergency operation (only visible if Notbetrieb YES)
1..3/
7/11
3/7/
11
-
Verd.m.Lab
w.AUS X
In the case of load shedding and system configuration with capacity-controlled compressors, one
complete compressor (with capacity stages) per load shedding stage is unloaded (only visible for
system configuration with capacity-controlled compressors: Anz.LS pro Verd. > 1)
Y/N N
-
Anz.Verfl.St
uf. X
Number of condenser stages
1..4/
8/12
4/8/
12
-
Freig.Verfl.
Stufen
→
Display of the condenser stages
→
Screen
3-1-e
Fremdlüfte
r X
Enable external fan YES/NO (only required when using a common condenser for 2 compressor
packs)
Y/N N
-
Lüftermast
er X
Enable fan master YES/NO (only visible if Fremdlüfter YES)
Y/N N
-
Lüfter CAN-
Adr. --
Entry of CAN Bus address: compressor pack that provides the external fans (only visible if
Fremdlüfter YES)
1..9,
–
–
-
Aussentem
p. XXX
Enable outdoor temperature sensor ON/OFF
ON/
OFF
ON -
Raumtemp.
XXX
Enable room temperature sensor ON/OFF
ON/
OFF
ON -
Feuchte X
Enable humidity sensor ON/OFF
ON/
OFF
OFF -
Kn.Nr
Umgeb.dat
XX
CAN bus address (node number) of the pack controller of which the ambient data should be used.
1..9,
–
–
-
Drucktrans
m.Z2 X
Pressure transmitter for Z2 available?
Y/N N
-