14.01.2019
146/185
VERD.STEU. POS:
XXXXX
Input
Defa
ult
Di
m.
U.BetrFreq[Hz]
Lower operating frequency of the FC compressor for compressor combined control (only
visible if the combined control type of control has been
selected - screen 3-2-1-1–a and the parameters MaxFreq.FU and MinFreq.FU are set to a
value other than "--").
15..45 30
Hz
Min.DrehzahlX.
XX
Minimum correcting variable in % for the compressor speed (only visible if the combined
control type of control has been selected - screen 3-2-1-1-a
and no values have been entered for MaxFreq.FU and MinFreq.FU).
0..15
0
%
Laufz.kl.Drehz
XXm
Maximum operating time [in minutes] of the FC compressor at low speed
10 - 60 15
m
Freq.Anh[Hz] --- Frequency in Hz that is increased to when FC compressor is operated at low speed for a
preset time.
20 - 60 ---
Hz
t Freq.Anh XXs
Duration of the frequency increase in minutes
5 - 60
15
s
P-Wert X.X
P-factor for PI controller for compressor speed control (only visible if the combined control
type of control has been selected - screen 3-2-1-1-a).
0.0..3.
0
0.7
-
I-Wert X.XX
I-factor for PI controller for compressor speed control (only visible if the combined control
type of control has been selected - screen 3-2-1-1-a).
0.00..1
.00
0.05 -
Intervall I X
Time interval for calculation of the I-component for PI controller for compressor speed
control (only visible if the combined control
type of control has been selected - screen 3-2-1-1-a).
1..30
1
-
Verz.FU-Verd.
Delay time until increase of the FC speed (after loading a fixed-speed compressor)
1..250 1
sec.
Handbetr.
Manual setting of the speed of an FC compressor ("---" = automatic)
0..100 ---
%
•
Screen 3-2-1-1-a Type of control
VERD.STEU. POS: XXXXX
Input Default
Dim.
Step controller
√
Selection list LP control type
√
√
-
Combined control
√
•
Menu 3-2-1-2 t0-shift
to-Schieb POS: XXXXX
Input
Defaul
t
Dim
.
to-shift
→
Selection list t0-shift
→
Screen
3-2-1-2-a
Max.Lastgrad XXX%
Minimum speed of the FC compressor for combined control (only visible if t0-shift
via consumer is active)
70..100 85
%
Min.Lastgrad XX%
Speed controller adjusting speed (I-Faktor) (only visible if to-shift via consumer is
active)
10..80
60
%