14.01.2019
57/185
Men
u
ECO POS: XXXXX
Description
Input
Defa
ult
Dim
.
3-2-4 Z2 Regulation
→
Selection menu Z2 Regulation.
The parameter must be set to "ECO operation" for the activation of the ECO
operation.
OFF
ECO-
Betrieb
TK-
Verdichter
OFF -
3-2-4 Temp.ECO EIN
XX °C
Switch-on temperature for the ECO operation solenoid valve
--: The switch-on temperature for the HRC ECO operation solenoid valve is
ignored.
--, 20..40
29
°C
3-2-4 T.ECO EIN WRG
Switch-on temperature for the HRC ECO operation solenoid valve when gas
cooler bypass is active
--: The switch-on temperature for the HRC ECO operation solenoid valve is
ignored.
--, 15..40
29
°C
3-2-4 Hysterese XX K
Difference for the ECO operation switch-on temperature, using which the
temperature
for the shutdown of the ECO operation is defined.
2..10
4
K
3-2-4 Min.ÖG MD-V
Minimum opening degree of the medium pressure valve for the enable of the
ECO compressors
10..80
60
%
3-2-4 Z2-Standzeit
Minimum standstill time of the ECO compressor
10..360
300
sec.
3-2-4 ECO-Verdichter * Activation of the ECO compressors
YES: ECO compressors are controlled via the VS 3015 C
NO:
ECO compressors are controlled
via a separate
VS 3010
Y/N
N
-
The following parameters are only visible if "ECO-Verdichter" = Yes
3-2-4
Anz. Z2-
Verdichter
Number of Z2 compressors
1..2
2
-
3-2-4 Basisz.LeiStu.
ON →
Display basic times t
b
ON
→
Screen
3-2-4-a
Screen
3-2-4-b
Screen
3-2-4-c
Screen
3-2-4-d
3-2-4 Vari.Z.LeiStu. ON
→
Display of the variable times t
v
ON
→
3-2-4 Basisz.LeiStu.
OFF →
Display basic times t
b
OFF
→
3-2-4 Vari.Z.LeiStu.
OFF →
Display of the variable times t
v
OFF
→
3-2-4 Regelkonstante
XX K
Max. control error for variable control times
1..15
3
K
3-2-4 Frei.M.Sch.Z2
Enable for the motor protection monitoring of the Z2 compressors
Y/N
Y
-
3-2-4 F.Öl/HD-St.Z2
Enable for the oil/HP monitoring of the Z2 compressors
Y/N
Y
-
3-2-4 P-Wert X.X
P-factor of the combined control for the Z2 compressors
Example: for control error of 1 K with a P-Wert of 1, the P-component is 1 V
0.0..3.0
0.7
V/K
Содержание VS 3015 C