WRG POS: XXXXX
Input
Default
Dim.
WRG-Betrieb X
Activate/deactivate HR mode
Y/N
N
-
The following parameters are only visible if HR.mode is activated (Y)
Laufzeit WRG XX h Maximum compressor run time in HR mode
1..10, – –
h
Standz. WRG XX m Compressor standstill time after disable via max.
operating time monitoring
30..180 60
Min.
Sollw.Schieb. X
Setpoint shift
Y/N
N
-
Off.ext.Sig X%
Offset for HR setpoint shift
0..25
0
%
Abtauendtemp X Defrost end temperature setpoint in heat pump mode 5..20
8
°C
HD-Soll ü CAN X
HP setpoint shift via CAN bus
Y/N
N
-
P-Korr.WRG XXB
Correction factor for high pressure setpoint calculation
in HR mode
0..10
0
b
HD-Max.WRG XXb Maximum high pressure in HR operation
75..95 82
b
HD-Min.WRG XXb Minimum high pressure in HR operation
50..80 75
b
•
Screen 3-2-3 MP control
MD-Reg. POS: XXXXX
Input
Default
Dim.
Soll MD XX b
Setpoint for medium pressure control
32..37
34.5
b
Dif. MD XX b
Difference from MP setpoint for activation of the pressure maintenance 1.5..6.0
1.5
b
ÜHV-Anheb./m X.XXb Ramp speed for increasing MP setpoint when
superheat is too small on the pack side
0.00..0.50 0.00
b
ÜHV-Absenk./m X.XXb Ramp speed for lowering MP setpoint when
superheat is large enough again on the pack side
0.03..0.50 0.10
b
ÜHK-Rampe/m X.XXb Ramp speed for MP setpoint shift when
superheat is too small on the case side
0.01..0.50 0.02
b
P-Wert XX b
Amplification factor Vp PI controller for MP control valve
0.0..5.0
0.7
-
I-Wert XXX b
Amplification factor Vi PI controller for MP control valve
0.00..0.99 0.8
-
Handbetr. XXX b
Manual setting of the MP control valve ("---" = automatic)
---, 0..100
—
%
•
Screen 3-2-4 Z2 regulation