14.01.2019
156/185
HD-REG POS: XXXXX
Input
Default
Dim.
Basisz. Verfl. ON
→
Setting of the basic times t
b
ON
→
Screen 3-2-2-2-
a
Screen 3-2-2-2-
b
Screen 3-2-2-2-
c
Screen 3-2-2-2-
d
Vari.Z. Verfl. ON
→
Setting of the variable times t
v
ON
→
Basisz. Verfl. OFF
→
Setting of the basic times t
b
OFF
→
Vari.Z. Verfl. OFF
→
Setting of the variable times t
v
OFF
→
Neutr.ZoneLXXK
Fan control switching hysteresis for step control
1..20
4
NZ_Drehz.reg.XK
Neutral zone for fan speed / combined control
0..8
2
RegelkonstanteXX K Max. control error for variable control times
1..15
10
•
Screen 3-2-2-2-a Basic time for condenser capacity stages ON
BASISZ.EIN POS: XXXXX
Input Default
Dim.
Basisz.EIN L1 XXX s
Only the available condenser capacity stages are displayed.
3..250 5
sec.
Basisz.EIN L2 XXX s
3..250 30
sec.
Basisz.EIN L3 XXX s
3..250 60
sec.
Basisz.EIN L4 XXX s
3..250 90
sec.
...
Basisz.EIN L12 XXX s
3..250 60
sec.
VS 3015 C base module: 1 - max. 4 capacity stages
with first SIOX extension module 1 - max. 8 capacity stages
with second SIOX extension module 1 - max. 12 capacity stages
•
Screen 3-2-2-2-b Variable time for condenser capacity stages ON
Vari.Z.EIN POS: XXXXX
Input Default
Dim.
Vari.Z.EIN L1 XXX s
Only the available condenser capacity stages are displayed.
3..250 20
sec.
Vari.Z.EIN L2 XXX s
3..250 120
sec.
Vari.Z.EIN L3 XXX s
3..250 180
sec.
Vari.Z.EIN L4 XXX s
3..250 250
sec.
...