Compressor shutdown for HP EMERGENCY OFF
All compressor stages are shut down immediately if the measured high pressure exceeds the limit value
HP
EMERGENCY OFF
(menu 3-3)
. A compressor enable is performed when the HP value has fallen below the
limit value
HP On Comp
(menu 3-3) again. They are then loaded again stage by stage. The error message "
HP
EMERGENCY OFF
" is generated if the high pressure exceeds the
HP EMERGENCY OFF
limit value.
Compressor shutdown in the case of high pressure fault
One compressor is unloaded if the high pressure exceeds the limit value
HP Off Comp
(menu 3-3). Other
compressors are unloaded with increasing high pressure. The unloading points for the other unloads are
dependent on the number of compressors and on the parameter
HP EMERGENCY OFF
(menu 3-3). The
switching intervals are calculated so that the shutdown of the last compressor is performed when reaching a
pressure of
HP EMERGENCY OFF
. While the limit value
HP Off Comp
is exceeded, any shifting down of the
compressor stages by the suction pressure regulation is still only performed using the basic switch-off time in
order to reduce the high pressure more quickly. If the limit value
HP Off Comp
has been exceeded, compressor
stages are not loaded again until the limit value
HP On Comp
has been undercut again. An exception is the
heat recovery mode. In the HRC and HRC Bypass modes. no compressor shutdown and no compressor
disable are performed but instead speed reduction (see Speed reduction in the event of high pressure fault
below). In heat pump operation (parameter
HRC-Pump
, menu 3-2-2-3), one capacity stage can be unloaded.
The HRC Bypass operation and heat pump operation are only possible in combination with a Coolheat or
ECOCool
controller.
Speed reduction in the case of high pressure fault (only for combined control)
If the compressor is controlled using combined control, the maximum compressor speed can be reduced with
rising pressure. The speed reduction depends on the parameters
HP Off Comp
,
HP On Comp
and
Weighting
C.OFF
(menu 3-3).
As default, the pressure reduction starts when the average value of
HP Off Comp
and
HP
On Comp
is exceeded. The start value can be shifted using the
Weighting C.OFF
parameter. A higher value
shifts the start point in the
HP On Comp
direction, a lower setpoint in the
HP Off Comp
direction and thus to a
higher pressure level.
The compressor speed is limited to Min. speed (parameter in menu 3-3) if the high
pressure reaches the
HP Off Comp
limit value.
High pressure fault alarm signalling
If the high pressure exceeds a limit value that is calculated using the parameters
HP Off Comp
,
HP On
Comp
and
Weighting C.OFF
(menu 3-3), the error message
High HP
is generated after a configurable time
delay (parameter
Del. tc/HP OFF
, menu 3-3). As default, the limit value is calculated from the average value of
HP Off Comp
and
HP On Comp
. The limit value can be shifted using the
Weighting C.OFF
parameter. A higher
value shifts the value in the
HP On Comp
direction, a lower setpoint in the
HP Off Comp
direction and thus to a
higher pressure level. No signal is generated In the heat recovery mode. In the event of any pending HP fault,
no additional compressor output stages are switched on. The following diagram is a graphical representation of
the entire HP monitoring using the example of a system with four compressors: